13 DG starting system?
Two 24VDC batteries
Auctioneered to use best battery
Cranks 13 DG at 75 rpm
13 DG starting sequence?
Cranks for 10 seconds
Waits for 10 seconds
Repeats 5 times
Total of 90 seconds
Then locks out starting circuits
13 DG ratings?
- Phases
- KW
- RPM
- Voltage
- Poles
3 Phase
1600 KW
1800 RPM
480 VAC
4 Poles
13 DG start sequence on loss of LC-107?
10 second time delay
Then 10 sec for DG up to volt/speed
701 trips (from Bus 13)
711 trips (to LC-108)
Then 710 closes (13 DG to LC-107)
When will 52-711 (LC-107/108 x-tie) auto close?
If 701 or 801 (from Bus 13 or 14) open with no fault, then 711 will close in less than 10 seconds to repower LC before 13 DG starts.
13 DG trips?
2160 rpm
Low L.O. press (30# for 9 sec)
High Coolant temp (225# for 10 sec)
Overcrank (90 sec)
Generator breaker trip
Manual
13 DG lube oil temp alarm?
230F
13 DG daytank high level?
95%
13 DG HI/LOW battery volts?
HI
: >30 V
LOW
: <24.4 V