-
What is Type III certification?
Maintaining, servicing, repairing, or disposing of low pressure appliances
-
How is leak detection different from other types?
Because a low pressure system operates below atmospheric pressure (in a vacuum) leaks in the gaskets or fittings will cause air and moisture to enter the system
-
What is the most efficient method of leak checking a low pressure unit?
- Pressurize the system by use of controlled hot water or heater blankets
- When controlled those are not feasible, use nitrogen to increase pressure
- Do not exceed 10 psig, which could cause the rupture disc to fail
-
How would you leak test a water box?
- Be certain the water has been removed before placing the leak detector probe through the drain valve
- To leak test a tube, use a hydrostatic tube test kit
- Systems with open drive compressors are prone to leaks at the shaft seal
-
When should crontrolled hot water be used to pressurize a system?
- For the purpose of opening the system for a non major repair
- Under EPA regulations a major repair mean involving the removal of any of the following components: compressor, condenser, evaporator, or any auxiliary heat exchanger coil
-
What are the leak repair requirements?
- Comfort cooling appliances containing more than 50 lbs should be repaired when leak rate exceeds 15%
- Commercial and Industrial process containing more than 50 lbs should be repaired when leak rate exceeds 35%
-
Describe the recovery techniques?
- A unit's high pressure cut-out is set for 10 psig when evacuating the refrigerant from a low pressure chiller and a rupture disc on a low pressure recovery vessel relieves at 15 psig
- Recovery from a system using R-11 or R-123 starts with liquid removal and is followed by vapor recovery
-
How would you prevent the freezing of water in a system?
- Water must be circulated through the tubes when evacuating refrigerant
- Most low pressure recovery machines utilize a water cooled condenser that is connected to the municipal water supply
- If a chiller is suspected of tube leaks, the water sides of the evaporator and condenser should be drained
-
What does the ASHRAE 3-1996 state?
If the pressure in a system rises from 1 mm Hg to a level above 2.5 mm Hg during vacuum testing, the system should be leak checked
-
What temperature should be attained when removing oil from a low pressure system?
- 130o F
- Fewer refrigerants are contained in the oil at this higher temperature
-
State some of the recharging techniques.
- Refrigerant is added through the lowest access point on the system, the evaporator charging valve
- However introducing liquid refrigerant into a deep vacuum will cause it to boil and may lower temperatures enough to freeze water in the tubes
- Intital charging is in the vapor tube, an R-11 system requires a vapor pressure of 16.9" hg or saturation temperature of 36o F
-
State the recovery requirements.
- Equipment manufactured after 11/15/93 must be certified and labeled by an EPA approved testing organization
- All equipment mst have low loss fittings to minimize refrigerant loss when hoses are disconnected
-
What are the required levels of evacuation for Low Pressure appliances? (before 11/15/93 and after)
- 25 inches Hg before
- 25mm Hg absolute after
- Once achieved, wait a few minutes and monitor the system pressure
- If pressure rises, there is refrigerant remaining in the system and recovery must be repeated
-
What are requirements of chillers using CFC-11 and HCFC-123?
- A purge unit
- Primary purpose is to remove non-condensables (air) from the system
- A centrifugal chillers purge condensing unit takes it suction from the top of the condenser, removes air from the system and returns refrigerant to the evaporator
-
How are systems protected from over pressurization?
- Low Pressure chillers typically use a rupture disc mounted on the evaporator housing
- The typical design burst pressure for a rupture disc is 15 psig
-
What is required for all ASHRAE saftey groups?
- Refrigerant monitor
- CFC-12, CFC-11 and HFC 134a are code grouped as A-1
- R-123 is code grouped as B-1
- All systems must be protected by a pressure relief valve, not in series
|
|