  1. A three-dimensional fire often involves static flammable liquid. true or false -
    false. 3D fires involve flammable liquid in motion as well as both horizontal and vertical surfaces.
  2. Class A fire extinguisher
    • are ok for wood, paper, some plastics and textiles.
    • They offer the coating effects of dry chemicals.
  3. Dry chemical stored pressure fire extinguishers
    should be removed or replaced at their next 6-year maintenance or hydrostatic test interval.
  4. Talking about UL rating, the _____ rating refers to the amount of sq footage an extinguisher covers.
    B:C
  5. Class B fire extinguishers cannot handle flammable liquid.
    False
  6. employees must be trained in proper use of all portable fire extinguishers according to
    CRF29
  7. you need to have portable fire extinguishers VISUALLY inspected.
    at least _____ according to 29 CFR 1910.157 (e) (2)
    monthly
  8. Class A/B fire extinguishers
    • should NOT be used for fire that involves live.
    • electrical equipment
  9. Water or steam fire extinguishers need to be discharged,
    disassembled and inspected at least:
    annually
  10. An extinguisher weighing over 40 lbs. should be installed so the top is.
    no more than __ from the ground
    3.5 ft
  11. OSHA specified maximum travel distance to an extinguisher for Class.
    B
    50 ft.
  12. dry chem extinguishers requiring 12 yr. hydrostatic test must be.
    emptied for maintenance procedures every.
    6 yrs.
  13. A rated UL extinguishers = how many gallons of water?
    1.25
  14. Class ____ fire extinguishers use electrically nonconductive extinguishing.
    agents
    C
  15. Cartridge operated water based portable extinguishers need.
    hydrostatic testing
    Every 5 years
  16. stored pressure type extinguishers need INTERNAL examination:
    never
  17. extinguishers weighing 40 lbs. or less must be.
    installed so top of canister is no more than _____
    5 ft above the ground
  18. class ___ extinguishers are for fires involving cooking media.
    K
  19. OSHA specified max travel distance for Class A is ______
    75 ft
  20. proper UL rating to use on electrically energized equipped.
    C
  21. work on the principle of saponification
    Class K
  22. involve flammable liquid on a horizontal surface w/ the
    presence of a solid object creating a barrier
    Obstacle Type Fires
  23. extinguishers must be installed at least _____ from the ground.
    4 inches
  24. may take place in flammable liquid storage cabinets,
    dip tank process areas, etc.
    Obstacle Type Fires
  25. To make sure the pressure gauges of CO2 extinguisher
    are showing adequate pressure, what must you do?
    Must Be Weighed
  26. Wetting agent portable extinguishers must be hydrostatic tested every.
    _____
    5 yrs.
  27. leak tests on stored pressure extinguishers must be.
    performed
    After recharge
  28. how do u convert fire extinguishers from 1 type to another?
    cannot
  29. may be reused.
    only if checked for proper type, contamination, and condition. closed recovery system.
    needs to be used!
    any remaining dry chemical in a discharged extinguisher
  30. New extinguishers needing charge in the field.
    • do not need to have any.
    • verification of service collar installed.
  31. how do u have an extinguisher converted to use a different type
    of extinguishing agent
    you cannot
  32. the gauge used to set the regulated source of pressure needs to
    be calibrated.
    annually
  33. pump tank calcium chloride-based antifreeze types of extinguishers
    need to be recharged.
    annually
  34. OSHA specified max distance to extinguisher for Class D
    75 ft.
  35. when you recharge, the amount of recharge agent to use should.
    be verified by
    weighing
  36. these types of extinguishers must
    have hydrostatic testing every 5 yrs.
    Aqueous Film Forming Foam (AFFF)
  37. The wetting agent in stored pressure wetting agent extinguishers.
    must be replaced.
    annually
  38. The premixed agent in liquid charge-type AFFF and FFFP
    extinguishers must be replaced every.
    3 yrs.
  39. cylinder-operated extinguishers
    • do not need to have any verification of
    • service collar installed.
  40. False - ANSWER-you are free to Mix multipurpose dry chemicals w/ alkaline based dry.
    chemicals
    False
  41. subsurface injection of wet chemical extinguishing agents
    into hot cooking media
    must be avoided.
  42. You should NEVER place extinguishers in cabinets or wall recesses.
    False
  43. how often must CO2 portable extinguishers go through hydrostatic testing?
    5 yrs.
  44. Pressurized gas fires and pressurized flammable liquids.
    Special Hazards
  45. Type ___ extinguishers w/ agents other than dry
    chemicals are not very effective on ______
    Type B, Special Hazards
  46. How do you filed adjust regulators that are utilized on
    wheeled fire extinguishers?
    Do not attempt.
  47. You do not need to keep permanent file record for each extinguisher.
    unless it has been in use for over 1 1/2 yrs.
    False
  48. Permanant File Record
    • needed for each extinguisher including:
    • maintenance date, name, and agency performing maintenance.
  49. Dry Nitrogen
    used as an expellant gas for stored-pressure fire extinguishers.
  50. connecting the fire extinguisher to the high pressure
    source for direct charging
    is not recommended
  51. the problem with halon agent is that it leaves a lot of residues after use.
    False
  52. the structural integrity of aluminum shells
    may be weakened when under fire exposure.
  53. The system used to rate effectiveness of extinguishers on Class B
    fires are applicable to pressurized flammable liquid.
    False
  54. Potassium base bicarbonate agents offer _____ capabilities when compared to sodium bicarbonate agents.
    greater - ANSWER-Potassium base bicarbonate agents offer _____ capabilities when compared to sodium bicarbonate agents.
  55. there are several types of dry chemical agents. the problem w/
    potassium chloride-based agent is that it is:
    Corrosive
  56. of all dry chemical agents, only
    ______ are suitable for Class A protection.
    Ammonium phosphate
  57. water type extinguishers are primarily for handling __________
    fires.
    Class A
  58. Backpack pump extinguishers should be avoided because they do
    not have a designated rating.
    False
  59. water mist extinguishers can only use________
    Distilled Water
  60. For safety, portable extinguishers should NOT be installed in a
    location accessible to the hazard.
    False
  61. all nonchargeable extinguishers come w/
    maximum useful life cycles of no more than______
    date printed on the nameplate.
  62. carbon dioxide extinguishers can be dangerous in
    unventilated locations
  63. Extinguishers should be CO2 or halogenated agent types when.
    computer equipment is in the location of fire.
    True
  64. what type of fires can Halotron fight?
    A, B, C
  65. suitable replacement for Halon 1211 because it is less.
    toxic and has 0 ozone depletion potential.
    Clean guard FE 36
  66. the pressure in a hydrostatic test of a cylinder shall maintained for a
    minimum of ____ sec.
    30
  67. dry chemical and dry powder
    on certain _ (cartridge operated)
  68. dry chemical and halogenated extinguishers
    • require 6 & 12 yr. hydrostatic.
    • testing
  69. water, afff, fffp, CO2 extinguishers
    • require 5 yr. maintenance and hydrostatic.
    • testing
  70. Class A rating
    wood
  71. class b rating
    2" depth heptane fires in square pans
  72. pressure gauges used on test equipment.
    calibrated semiannually.
  73. if cylinder has welding, broken threads, nicks or corrosion.
    Condemn
  74. master gauges
    calibrated annually
  75. drying equipment
    shall not exceed 150F.
  76. DOT 3E cartridges or TC 3EM cartridges
    exempt from periodic hydrostatic testing.
  77. hydrostatic test of cylinder shall be maintained for
    30 seconds
  78. test pressure for hose assemblies
    maintained for min of 1 min.
  79. when not specified, shall be tested to factory test
    pressure, not exceeding 3x's service pressure
    low pressure cylinder
  80. cartridge operated extinguishers
    tested at original factory test pressure.
  81. DOT3A 3AA 3AL cylinders tested @ 5/3 service.
    pressure
    High Pressure Cylinders
  82. tested at 3000 psi.
    CO2 extinguishers w/ ICC3 specs
  83. CO2 hose assemblies
    tested at 1250psi.
  84. Dry Chem, Powder, water, foam, halogen hose assemblies
    • 300psi or
    • service pressure (whichever is higher)
  85. low pressure accessory hose on wheeled extinguishers
    tested at 300psi
  86. high pressure hose on wheeled extinguishers
    tested at 3000psi.
  87. hose assemblies that pass hydrostatic testing
    • shall not require recording.
    • labeling or marking
  88. property owner
    assumes role of authority having jurisdiction
  89. class a hazards
    travel distance is from any point to extinguisher.
  90. class B, D, K hazards
    travel distance is from hazard to extinguisher.
  91. HMIS
    Hazardous Material Identification System
  92. minimum discharge duration for extinguisher rated at 2A or
    higher
    13 seconds
  93. water type, halogenated, multipurpose dry.
    chemical, wet chemical
    Class A Hazard extinguishers
  94. Class B hazard extinguishers
    • AFFF, FFFP, CO2, Dry Chemical,
    • Halogenated
  95. class a hazard installation minimum # of extinguishers -
    • divide total floor area.
    • by maximum area to be protected per extinguisher
  96. smaller extinguishers rated class b or c
    • shall not be used if they don't meet.
    • minimum 1-A rating
  97. up to 2 water type extinguishers with 1-A rating can be used.
    to fulfill rating of 1 2-A extinguisher
    True or False
  98. 2 2 1/2 shall be permitted to fulfill requirement of 1 4-A rated.
    extinguisher
    True or False
  99. light hazard class A
    2-A, 3000ft, 11250ft
  100. calcium chloride ok for use in stainless steel extinguishers
    True or False
  101. carbon dioxide hose assembly
    • must pass annual CONDUCTIVITY test with