Hydrostatic testing NFPA 10 chapter 5

  1. IF________is used as a sole medium for pressure
    testing, or if all air is not vented from the vessel prior to hydrostatic testing, the failure of the fire extinguisher vessel will be violent and dangerous.
    air or gas
  2. The equipment for testing low pressure cylinders includes a hydrostatic test pump, hand or power operated, to be capable of producing not less than_______percent of the test pressure.
    150
  3. The equipment for testing equipment and cartridges shall be of the water-jacket type that meets the specifications of the pamphlet Methods for Hydrostatic Testing of Compressed Gas Cylinders, published by____________.
    the Compressed Gas Association
  4. The hydrostatic test interval for the following types of extinguishers is_____years:

    • AFFE
    • FFFP
    • wetting agent
    • carbon dioxide
    • dry chemical with stainless steel shells stored pressure water, steam, and/or antifreeze
    5
  5. Where a fire extinguisher cylinder or shell has been repaired by soldering, welding, brazing,or the use of patching compounds,_________.
    it shall not be hydrostatically tested, but shall be destroyed
  6. Fire extinguishers that are required to be returned to the manufacturer for recharging shall be hydrostatically tested
    Only by the manufacture
  7. The pressure in a hydrostatic test of a cylinder shall be maintained for a minimum of________
    seconds, but for no
    less time than is required for complete expansion of the cylinder and to complete the visual examination of the cylinder.
    30
  8. The hydrostatic test label of low pressure cylinders shall include
    All of the above
  9. The hydrostatic test interval for the following types of extinguishers is years:

    •dry chemical, stored pressure, with mild steel shells, brazed brass shells, or aluminum shells
    • dry chemical, cartridge, or cylinder operated, with mild steel shells
    • halogenated agents
    • dry powder, stored pressure, cartridge- or cylinder-operated, with mild steel shells
    12
  10. The hydrostatic test label for a low pressure type fire extinguisher shall be affixed to the shell by
    a heatless process
  11. Dry chemical and dry powder hose assemblies requiring a hydrostatic pressure test shall be tested at
    or at service pressure, whichever
    is higher.
    300 psi
  12. Drying equipment is required to dry all nonwater types of fire extinguishers that have passed the hydrostatic test.
    True
  13. Where a fire extinguisher cylinder or shell has corrosion that has caused pitting, including pitting under a removable nameplate or nameband assembly,
    it shall not be hydrostatically tested, but shall be destroyed
  14. For high pressure cylinders and cartridges passing a hydrostatic test, the month, year, and the DOT identification number shall be stamped into the cylinder in accordance with the requirements set forth by
    DOT or TC
  15. The equipment for testing low pressure cylinders includes a flexible connection for attachment to the test pump. It shall be provided with necessary fittings to test through the fire extinguisher
    • Nozzle
    • Test bonnet
    • Hose outlet
  16. Before hydrostatic testing, all
    extinguishers shall have the valve removed from the cylinder and replaced with a suitable test bonnet or adapter.
    Stored pressure
  17. All stored-pressure fire extinguishers shall be hydrostatically tested at the factory pressure not to exceed
    the normal operating pressure.
    three times
  18. The exception to the standard service pressure ratio for testing carbon dioxide fire extinguishers is that carbon dioxide fire extinguishers having cylinder specification
    ICC3 shall be tested at
    psi.
    3,000
  19. The equipment for testing low pressure cylinders includes
    for personnel protection.
    A protective cage and barrier
  20. Where fire extinguisher shells, cylinders, or cartridges fail a hydrostatic pressure test, they shall be
    destroyed by the owner or at his or her discretion
  21. Fire extinguishers having aluminum cylinders or shells suspected of being exposed to temperatures in excess of
    shall be removed from service and
    subjected to a hydrostatic test.
    350°F
  22. Where a calcium chloride type of extinguishing agent was used in a stainless steel fire extinguisher,
    it shall not be hydrostatically tested, but shall be destroyed
  23. A hydrostatic test pump, hand-operated or power-operated, shall be capable of producing not less than percent of the test pressure.
    150
  24. Cartridge- or cylinder-operated dry chemical and dry powder types of fire extinguishers shall be hydrostatically tested at
    their original factory test pressure as shown on the nameplate or shell
  25. For hydrostatic testing, all types of extinguishers except shall have all traces of extinguishing
    agents removed from inside of the extinguisher before filling with water.
    Water Type
  26. A hydrostatic test shall be performed on fire extinguisher hose assemblies
    equipped with a shutoff nozzle at the end of the hose
  27. Fire extinguisher shells of the low pressure type that pass a hydrostatic test shall have the test information recorded
    on a suitable metallic label or equally durable material
  28. Any person holding a fire extinguisher license may perform hydrostatic testing.
    False

    Hydrostatic testing shall be performed by persons trained in pressure testing procedures and safeguards, and having available suitable testing equipment, facilities, and appropriate servicing manuals
  29. Hose assemblies passing a hydrostatic test do not require recording.
    True
  30. AIL
    wheeled extinguishers shall
    have pressure relief devices removed prior to hydrostatic testing.
    • Cartridge-operated
    • Cylinder-operated
  31. Hose assemblies of carbon dioxide fire extinguishers that require a hydrostatic test shall be tested
    Within a protective cage
  32. Dry chemical, dry powder, water, foam, and halogenated agent discharge hose assemblies requiring a hydrostatic pressure test shall be tested at or at service pressure, whichever is higher.
    300 psi
  33. Nitrogen cylinders or cartridges used for inert gas storage used as an expellant for wheeled fire extinguishers shall be tested every years.
    5
  34. itrogen cylinders and carbon dioxide cylinders used ith wheeled fire extinguishers shall be tested at e service pressure as stamped into the cylinder.
    5/3
  35. In addition to the visual examination required for high pressure cylinders prior to testing, an internal examination shall be made prior to the hydrostatic test.
    True
  36. Ill air shall be vented prior to hydrostatic testing to revent
    dangerous failure of the cylinder
  37. A complete internal and external visual examination shall be conducted following any hydrostatic test.
    False
  38. Nitrogen cartridges and carbon dioxide cartridges used as an expellant for hand portable fire extinguishers that have DOT or TC markings shall be hydrostatically tested or replaced according to the requirements of DOT or
    TC, with the following exception(s):
    Cartridges with DOT stamp 3E are exempt from periodic hydrostatic retesting

    Cartridges not exceeding 2 inches outside diameter and having a length less than 2 feet are exempt from periodic hydrostatic retesting.
  39. Fire extinguishers shall be hydrostatically tested at intervals not exceeding those specified in table 5-2 of
    NFPA 10, with the following exception(s):
    • Fire extinguishers utilizing a cylinder that has DOT or TC markings shall be hydrostatically tested, or replaced, according to the requirements of DOT
    • ог TC.

    For fire extinguishers not covered in A above, the first retest may be conducted within 12 months of the specified test intervals.
  40. Carbon dioxide fire extinguishers shall be tested at the service pressure as stamped into the cylinder.
    5/3
  41. The hydrostatic testing of
    fire
    extinguishers having an externally mounted gas cartridge shall have the cartridge and cartridge receiver removed and a suitable plug inserted into the opening.
    dry chemical

    dry powder
  42. NFPA 10, 5-1.3 states,
    "If, at any time, a fire extinguisher
    shows evidence of corrosion or mechanical injury, it shall be hydrostatically tested.
    The exception(s) to this rule is(are)
    pump tanks

    nonrechargable fire extinguishers other than halogenated types shall be discharged and discarded

    nonrechargable halogenated agent type fire extinguishers
  43. Carbon dioxide hose assemblies requiring a hydrostatic pressure test shall be tested at
    1,250 psi
Author
jdealarcon
ID
362273
Card Set
Hydrostatic testing NFPA 10 chapter 5
Description
Updated