CDC 3E051A Vol.2 Unit 2

  1. What number is the maximum ohmic reading for static grounds according to current Air Force directives?




    C) 10,000
  2. An equipment ground is a grounding system that




    A) Connects to earth all nonconcurrent carrying metal parts of an electrical wiring system.
  3. What maximum ground resistance is the value for an electrical system with a voltage of 600 volts alternating current (VAC) or less?




    B) 25 ohms
  4. During which season could you expect to measure the lowest ground reading?




    C) Spring
  5. Which location is the correct location for grounding a system neutral?




    A) Source side of service entrance
  6. A system neutral conductor is likely grounded improperly (grounded on the load side of the service entrance disconnect), if the ohmic value is less than




    A) 20K
  7. At what intervals should a wye-connected distribution system neutral be grounded?




    C) At a distance not to exceed 1/4 mile.
  8. What recommended depth is the top of a ground rod driven for distribution pole grounding?




    B) 2 feet below ground level.
  9. The metal frame of a building can be used as a facility ground




    D) if the frame is effectively grounded.
  10. What are the requirements for a facility ground rod?




    B) 8 feet long; copper-clad steel, solid copper, or stainless steel.
  11. Which is the maximum allowed resistance for an electrode used for communications network grounds?




    B) 10 ohms
  12. Isolated ground (IG) receptacles are used in circuits feeding electronic devices to




    A) minimize noise.
  13. In an isolated ground (IG) receptacle, the




    B) grounding pin is purposely insulated from the outlet box.
  14. What happens if a bare grounding wire touches the hot conductor terminal of a receptacle inside of a properly grounded outlet box?




    C) The circuit breaker for that circuit trips.
  15. Physical failure of grounding systems usually occurs in which portion of the system?




    D) Just above and below ground level.
  16. In an interior wiring system with metallic conduit, through how many possible paths can return ground fault flow?




    B) Two
  17. What test can you perform to ensure that the above grade components in a grounding system have a low resistance path to ground?




    B) Continuity test.