Third Step "A"

  1. What is the term for conductors that originate at the terminals of a circuit breaker or a circuit recloser in a distribution substation and continue to the termination point of the high side of distribution transformers?




    D) Distribution feeder circuits
  2. A study of 10 linemen who regularly worked on energized 345 KV transmission lines
    conducted by personnel at John Hopkins University for a 10 year period concluded
    what about the health of the linemen?




    A) The linemen were in excellent health
  3. Why are direct current transmission systems used?




    B) To interconnect two AC systems which are not synchronized
  4. Given a primary metering installation on a 13,200 / 7,620 volt system with the primary WYE connected to the voltage transformer and a secondary voltage of 120 volts, what is the turn’s ratio of this voltage transformer?




    D) 63.5/1
  5. What does the term LSC stand for?




    B) Light sensitive control
  6. What is the term to describe a luminous discharge created by the ionization of air surrounding an electrical conductor?




    D) Corona
  7. What would cause an ATO to switch from the preferred feed to the alternate feed?




    B) A power interruption on the preferred feed for a preset amount of time
  8. Why is the capacity of an underground transmission system severely limited when cables are installed in ducts?




    D) The duct limits the cables ability to dissipate heat generated in the cable
  9. High-pressure, oil-filled, paper-insulated cables in which three phase conductors are enclosed in a steel pipe containing oil are used for underground transmission circuits.
    True
  10. Phase sequence has no effect on poly-phase motors.
    False
  11. How is an electronic sectionalizer reset?




    B) Install a new actuator and close the gate with a hotline tool
  12. An auto booster with a 10/1 ratio (boosting) is on a line where the source voltage measures 6,927 volts.
    The sliding contact is on tap 5 of the secondary coil. What is the corrected voltage on the load side of the auto booster?




    B) 7,620
  13. What should be done before replacing a three-phase transformer?




    B) Rotation should be checked, marked and returned the same way
  14. What is the bank KVA rating of two 50-KVA transformers that are connected in an open delta configuration?




    B) 86.6 KVA
  15. What does a yellow dot on the outside of a secondary pedestal indicate?




    D) The pedestal feeds a streetlight
  16. A 25 KVA transformer has a ratio of 27.5 to 1. If the primary voltage is 13,200, what is the rating of the secondary in KVA?




    D) 25
  17. If given a metering installation involving current transformers, what must be done prior to working on the secondary side of a current transformer for safety?




    C) The CT must be shunted or bridged to prevent primary potential on the secondary side
  18. If a customer needs 240 volt three-phase service, what secondary rating on the nameplate can be used?




    C) 240 / 480
  19. How many times will our field reclosers operate before they lockout?




    D) Three operations and then lockout
  20. There are three different types of substations. What are they?




    B) Transmission, sub-transmission, and distribution
  21. What type transformer is used in a series street lighting circuit?




    C) Constant current
  22. What device uses air, oil, SF6, gas or vacuum to break the arc when switching electrical circuits and equipment in and out of the system?




    C) Circuit breakers
  23. There are four basic types of switched capacitor banks. Which of the following are
    switched capacitor banks?




    A) Voltage, current, VAR, and Temperature
  24. What is the safest way of completing electrical distribution work?




    D) De-energize, isolate, test, and ground
  25. When taking a regulator off line, after confirming the regulator is in the neutral position, what should be done before closing the bypass switches?




    D) The selector switch should be turned to the off position
  26. What is a clearance tag to be considered the same as?




    A) A lock
  27. ATO’s are installed to meet what customer requirements?




    D) Customers with essential loads who require two electric sources with automatic transfer from one source to the other
  28. What equipment reduces primary voltage to the utilization voltage required by the customer?




    B) A distribution transformer
  29. If the regulatory tap setting on a single-phase transformer is changed from tap C
    (100%) to tap D (97.5), what happens to secondary voltage?




    C) It will increase
  30. What does the number 25 on a luminaire indicate?




    A) 250 watts
  31. Converter stations are used to convert AC transmission voltages to DC, and
    vise-versa.
    True
  32. When paralleling transformers, what is the maximum allowable difference in rated impedance between the transformers?




    D) Within 7.5% above or below each other
  33. On a WYE / WYE bank, the primary neutral is floated to prevent excess voltage from building up on the secondary side.
    False
  34. Auto Boosters automatically adjust to changing loads and voltages.
    True
  35. What should be used to energize and de-energize oil filled equipment?




    D) Appropriate insulated sticks
  36. Why should rubber gloves be stored in canvas bags when not in use?




    B) To protect them from mechanical damage or deterioration from ozone
  37. A sectionalizer is found tripped. You patrolled the lines find nothing wrong and call dispatch for permission to close it back in. How do you close the sectionalizer back in?




    C) Push up on the yellow ring with a hot line tool
  38. What does protective equipment provide the lineman?




    A) A margin of safety for error without injury
  39. What are the two types of capacitor banks?




    D) Fixed and switched
  40. What is the purpose of current transformers used in substations?




    D) To measure high current by reducing it proportionally to a manageable level
  41. Given a 101 KVA or larger single phase overhead transformer, how many secondary bushings would you generally expect it to have?




    D) Four
  42. What is the most likely cause for a streetlight burning during daylight hours?




    D) The photocell has failed
  43. The need for a neutral is minor when the load is balanced among the three phases. For this reason, the neutral is often omitted in distribution and
    transmission wye circuits.
    True
  44. Once secondary phase conductors have been removed from an energized
    overhead transformer, they should be considered energized until the connection
    status of both ends of the secondary mains are verified open and not paralleled
    to another transformer.
    True
  45. What are the two main reasons linemen wear safety hard hats?




    B) To protect the head from the impact of falling or moving objects and electrical contact
  46. What is the phase to ground voltage in a 4160 four wire system?




    D) 2400 volts
  47. Which of the following is true of a transformer nameplate listing one secondary voltage of 277 volts?




    D) The transformer has only one secondary coil
  48. In addition to ensuring percent impedance of one transformer is between 92.5% and 107.5% of the other transformer, which of the following conditions must be met in order to parallel two single-phase transformers for greater capacity?




    D) Only B and C
  49. Which situation will cause a substation breaker to operate automatically?




    D) All the above
  50. Given a transformer that has a high side winding made with small wire and a large
    number of turns and a low side winding that is made with larger wire and a fewer
    number of turns, what type of transformer is this?




    D) Step down transformer
  51. What is the best rubber cover up component to use to cover up odd shaped conductors and equipment?




    A) A rubber-insulating blanket
  52. What test should be performed on rubber gloves before work each day?




    B) Air test
  53. Conductor covers, insulator covers, and cross arm covers are fabricated from rubber
    and what other material?




    A) High dielectric polyethylene
  54. A sectionalizer is normally set to lockout at ________ count(s) less than the recloser lockout.




    D) 1
  55. Class 0 rubber gloves are AC proof tested to __________ volts rms and DC proof
    tested to __________ volts average.




    C) 5,000 and 20,000
  56. Fuses are installed to protect the electrical system from what?




    B) Faults and short circuits
  57. What is the purpose of a lightning arrester in a distribution circuit?




    B) To bypass electrical surges on the circuits, protecting the insulators and equipment from over voltages
  58. An Auto booster is capable of lowering the voltage on a distribution line.
    True
  59. What is the most common type of lamp used by this company?




    C) High pressure sodium
  60. What is the voltage required by the primary winding in a transformer that has
    2,400/4,160Y 120/240 on its nameplate?




    C) 2400 volts
  61. Primary metering is a cost saving installation that benefits the company and customers that use large amounts of power.
    True
  62. Which of the following is true regarding a three phase delta circuit?




    D) All the above
  63. Reactive kilovolt-amperes can be supplied to the electrical system by connecting___________ to the distribution circuits in the substations or out on the distribution lines to neutralize the effect of customer inductive loads.




    B) banks of capacitors
  64. How is an insulator hood properly installed?




    C) It will overlap the line hose when properly installed
  65. To keep from damaging underground cable when pulling it in, you must not pull beyond its maximum allowable tension or bend it greater than its allowable radius.
    True
  66. What device is used to check for a bad cell in a de-energized capacitor rack?




    A) C-meter or microfarads meter
  67. Auto boosters can only boost or only buck depending on how they are wired.
    True
  68. What do voltage or potential devices connected to coupling capacitors normally provide
    power to?




    D) Protective relays
  69. Which of the following are methods of controlling light emissions from streetlights?




    D) Reflectors, refractors and diffusing globes or a combination are used to direct and control light
  70. How should rubber-insulating sleeves be treated by the lineman?




    A) Rubber sleeves must be treated with care and inspected regularly by the lineman
  71. What is the preferred method for de-energizing a switched capacitor bank?




    C) Open switch in the control box with class two rubber gloves
  72. What is the term for a transformer that contains protective devices such as lightning arrestors, primary fuses and secondary breakers?




    C) CSP transformer
  73. How is voltage regulation on any electrical system defined?




    B) The difference in voltage between periods of no load and periods of full load on the system
  74. What is calculated when the resistance, inductive reactance, and capacitive reactance are considered to determine the total opposition to current in a circuit?




    C) Impedance
  75. How are rubber goods easily damaged?




    A) Only Improper storage and Exposure to grease and oil
  76. After washing rubber gloves, what is the best thing to do next?




    C) Rinsed thoroughly and left to air dry
  77. When using a voltmeter to perform phasing on two known energized secondary circuits, what does a “0.00” reading indicate?




    C) The two circuits being tested are the same phase
  78. What is used to cover primary distribution conductors to protect the lineman from an accidental electrical contact?




    A) Rubber insulating line hose
  79. What is the maximum use voltage for class 2 rubber gloves?




    D) 17, 000 volts ac rms
  80. What is the most important article of protection for a lineman or cableman?




    A) A good pair of rubber gloves with proper dielectric strength
  81. Which of the following is true concerning a transformer with the following voltage rating on the nameplate:12,470GRDY/7,200?




    C) Indicates the transformer has reduced insulation at the neutral end of the primary coil
  82. What is the function of a protective relay in a substation?




    A) Automatically operate their contacts to properly identify the source of the trouble and remove it from the electrical system
  83. What procedure must be completed before connecting two energized secondary wires
    together?




    A) Use a voltmeter to ensure the phasing is correct
  84. Each work project and especially those projects requiring linemen and cablemen to handle energized electrical conductors should be planned in detail. What should this plan ensure?




    C) The safety of the workers and the reliability of the electrical service
  85. What is the purpose of capacitor banks installed on distribution circuits?




    B) To improve the power factor
  86. There are two types of distribution regulators now in service. They are the induction and the step voltage regulators.
    True
  87. What causes a voltage drop in an electric circuit that causes voltage to be less at the load end than it is at the source end of a line?




    C) Current flowing through the line impedance causes a voltage drop
  88. Image Upload 2 What type of transformer connection is shown by the illustration?




    C) Delta - Wye
  89. Current and potential transformers supply the intelligence for measuring power flows and the electrical inputs for the operation of protective relays associated
    with the transmission and distribution circuits.
    True
  90. The voltage variation to residences (secondary) has been standardized. What are the low and high limits?




    C) 114 and 126
  91. How many steps does an auto booster have, not counting the neutral position?




    C) 5 steps wired for either boost or buck but not both
  92. What component is used to regulate voltage on a line when capacitors are no longer
    effective?




    D) All the above
  93. What should be done with metal structures and fences that are constructed under extra high voltage transmission lines?




    B) Metal portions should be effectively grounded to bleed off static charges
  94. What does the acronym “SCADA” stand for on an automated distribution system?




    D) Supervisory Control and Data Acquisition
  95. What limits the capacity of overhead AC transmission lines?




    A) Thermal expansion and resulting sag of line conductors
  96. What happens to the current on the neutral of a wye system when the loads between
    the phases are not balanced?




    A) The current goes up on the neutral
  97. A sectionalizer senses fault current at what percentage of its operating current rating?




    D) 160%
  98. What is the term for a direct current transmission line consisting of one conductor with the ground as a return?




    A) Monopolar DC system
  99. What is the purpose of a sectionalizer?




    C) Isolates faults and protects the feeder and distributor
  100. On a delta circuit, there is no return current through the ground.
    True
  101. Your mother is incredibly proud of the man you have become!
    True