SIB 33

  1. What are some the reason to perform Bk switching
    • a. To maintain a bus voltage in distributing stations which will keep a maximum number of feeder regulators within operating range.
    • b. To reduce short circuit duty on 4.8 kV or 4.1 kV circuit breakers.
    • C. To maintain scheduled bus voltage on receiving station 34.5 kV buses.
    • d. To maintain sufficient bank in service capacity to safely carry the station load and meet the normal minimum requirements for receiving stations specified in Station Instruction Bulletin 27, paragraph 9.
    • e. To provide for CLEARANCE or OKs TO 
    • f. To isolate grounded 4.8 kV circuits or equipment from circuits or equipment which are clear of grounds.
  2. Why should banks be energized from the high side (power supply side)
    To avoid the inrush of exciting current current which is great enough to cause voltage disturbances to consumers, should a bank be energized from load buses, supplied by another bank
  3. Why do we used Bank in Service Caps
    To prevent the unintentional operation of CB
  4. Why don't place Bank in Service caps on open CBs
    It can lead to wrong assumption that the CB is closed, and result in dropping load
  5. Why are BIS caps not used when on System Control
    When bank switching is done by ECC, BIS caps may remain on CB control handles of a bank that has been switched out, conversely and bank that is in service will not have BIS caps
  6. What is the only way to determine if disconnects are actually closed
    Visual confirmation
Author
Benjammincash
ID
356271
Card Set
SIB 33
Description
Bank Switching
Updated