In a majority of our distributing stations differential bus protection is not provided for the distribution buses.
True
An unexpected overload of limited duration caused by some unforeseen disturbance of normal operation
An emergency short-time overload
150% of full load (50% overload) may be safely carried approximately and that 200% of
full load (100% overlaid) may be safely carried approximately , following full load in both instances.
45 minutes, 11 minutes
What is the limiting factor in short-time overloading of a transformer
The hot spot temperature, which not exceed 95° C
Overloading
60sec
5min
30min
2hr
FL - 370% NL - 470%
FL - 230% NL - 300%
FL - 160% NL - 190%
FL - 125% NL - 140%
True/False
Top oil temperature will usually accurately reflect the
winding or hot spot temperature after two hours of load. If transformer top oil temperature
exceeds 80° C for a self cooled transformer or 65° C for a water cooled transformer advise the Area
Supervisor or Chief Operator and secure managements advice on procedure