SIB 11

  1. True/False

    In a majority of our distributing stations differential bus protection is not provided for the distribution buses.
    True
  2. An unexpected overload of limited duration caused by some unforeseen disturbance of normal operation
    An emergency short-time overload
  3. 150% of full load (50% overload) may be safely carried approximately                  and that 200% of
    full load (100% overlaid) may be safely carried approximately     
                    , following full load in both instances.
    45 minutes, 11 minutes
  4. What is the limiting factor in short-time overloading of a transformer
    The hot spot temperature, which not exceed 95° C
  5. Overloading 
    60sec
    5min
    30min
    2hr
    • FL - 370% NL - 470%
    • FL - 230% NL - 300%
    • FL - 160% NL - 190%
    • FL - 125% NL - 140%
  6. True/False

    Top oil temperature will usually accurately reflect the 
    winding or hot spot temperature after two hours of load. If transformer top oil temperature 
    exceeds 80° C for a self cooled transformer or 65° C for a water cooled transformer advise the Area 
    Supervisor or Chief Operator and secure managements advice on procedure