7.4

  1. True/False
    At generating stations, the generators produce power at voltages between 12,000 and 25,000 volts
    True
  2. The transformers on our system fall into three classes
    • Power Transformers
    • Transformers that handle energy in large quantities.
    • Distribution Transformers
    • Transformers that furnish energy at service voltages.
    • Instrument Transformers Transformers that reduce operating voltages and currents to levels
    • suitable for instrumentation or protective relays.
  3. True/False

    There are two types of instrument transformers: potential transformers and current transformers
    True
  4. True/False

    A transformer is basically two sets of coils on a magnetic core of some kind. It has no moving parts and works on the principle of mutual induction.
    True
  5. True/False

    Turns-ratio is the number of turns of wire in the primary winding compared to the number of turns in the secondary winding
    True
  6. True/False

    When the number of turns or voltage on the secondary is less than that of the primary, the transformer is known as a Step-down Transformer.
    True
  7. True/False

    When a load is applied to the secondary windings, load current will appear in both windings. These currents are inversely related to the turns-ratio of the windings.
    True
  8. The flow of current in the primary circuit is governed by three factors
    • Characteristics of the source
    • voltage and frequency
    • Impedance of the winding
    • Strength and direction of the magnetic field in the iron core
  9. The voltage induced in the secondary coil is also governed by three factors:
    • Strength and direction of the magnetic field in the iron core
    • Rate of change in the magnetic field
    • Number of turns in the coil
  10. Core loss is the sum of               and              losses
    eddy-currents, hysteresis
  11. True/False

    Hysteresis losses are the result of the molecules of the core material being magnetized and de-magnetized
    True
  12. True/False

    Copper losses are an additional transformer loss. They are due to the resistance of a transformer winding to the magnetizing current
    True
  13. True/False

    Transformer losses dissipate power and produce unwanted heat that must be removed
    True
  14. The purpose of the tank is to contain the             and            , and the oil they are immersed in
    core, windings
  15. Oil in a transformer has two purposes:
    • Insulating the transformer
    • Cooling the transformer
  16. A combination of power transformers used to energize three-phase loads. Banks may be made up of three single-phase or a single unit. Mobile unit banks can be transported to stations for emergency replacement.
    Banks
  17.               banks are large transformers used at switching and receiving stations to change the voltage between sections of a bus
    Bus
  18.               banks are large transformers used at switching and receiving stations to change the voltage between a line and a bus
    Line
  19.                     are instrument transformers that
    measure voltage
    Potential transformers (PT)
  20.                     are instrument transformers that
    measure current.
    Current transformers (CT)
  21.                   transformers are power transformers used on the
    distribution system. These transformers may be on poles
    overhead, on ground level pads, or in underground structures
    Distribution
  22.                      are potential devices connected to the system through capacitors. CCPDs are used for metering
    Coupling Capacitor Potential Devices (CCPD)
  23. A transformer is basically two sets of coils on a magnetic core of some kind. It has no moving parts and works on the principle of                    .
    mutual induction
  24. True/False

    The insulating ability of transformer oil depends on its being
    completely free of contaminants, water and oxygen in particular.
    True
  25. True/False

    In order to prevent pressure build up in sealed tank units, some transformers have breathing regulators.
    True
  26. Both the                  approach and the                   allow atmosphere into the space above the oil. The regulator allows both water vapor and oxygen in.
    breathing regulator, desiccant breather
  27.                is used in the space above the oil. An automatic pressure relief valve is connected to the gas space so that when the internal pressure reaches 5 psi, gas is vented to reduce the pressure.
    Nitrogen (N2)
  28. True/False

    In a Transformer, Pressurized nitrogen is connected to the gas space. This maintains a positive pressure in the gas space that mitigates against entry of air through leaks
    True
  29. Oil heated in and around the windings and core rises to the top of the tank. This oil is replaced by cooler oil from the bottom of the tank in a circular motion
    convection process
  30. The                  of the transformer is determined by the rate of heat flow from the coils and core
    MVA rating
  31. The maximum top oil temperature is                for normal transformer operation
    95°C
  32. What are three general methods for increasing cooling rate seen in DWP transformers:
    • 1. Increase Surface Area of Tank.
    • 2. Increase the Rate of Air Movement.
    • 3. Increase the Rate of Oil Circulation.
  33. A transformer is considered                    when it is equipped with radiators accept oil from the top of the tank and separate it into several paths. This exposes the oil to a large surface through which its heat can move to the surrounding air.
    self-cooled
  34. As heat is transferred from the metal to the air it is in contact with, the air expands, becomes less dense, and rises.
    Cooler air from the surroundings flows in to take its place. This air, in turn, is heated and rises. Cooler air from the surroundings flows in to take its place
    natural convection
  35. True/False

    A self-cooled transformer can be identified on its nameplate by the letters OA signifying Oil to Air.
    True
  36. A transformer with thermostatically controlled fans has two ratings:
    1. Self-cooled rating
    2. Forced convection rating.
    How are these ratings identified on a Nameplate
    OA/FA
  37. The letters                 are used on the nameplate to signify forced oil to air heat transfer capability
    FOA
  38. True/False

    The power banks high side might include a no load tap changer with a five-position range. If the high voltage side is 230kV the range would be from 220kV to 240kV in 5kV increments
    True
  39. True/False

    The low side of the same power bank might include a load tap changer with a 33 position range. If the low voltage side is 34.5kV the range would be from 32.4kV to 39.6kV in approximately 120V increments
    False - 220V
  40. Due to variations on the primary side of distribution               transformers, taps are changed to maintain a constant on the secondary
    voltage
  41. If the current in the low voltage winding is very high or if the voltages of both windings are above 33kV the use of a             is desirable.
    series transformer
  42. Transformers having a single coil configuration are called 
                     
    autotransformers
  43. True/Fasle

    Autotransformers are much cheaper to produce than two coil
    transformers of the same rating. The disadvantage is that the primary and secondary circuits are electrically connected and therefore cannot be safely used to stepping down voltages for consumer use.
    True
  44. The application of wye connected transformers led to the use of a third transformer winding, referred to as a               winding
    tertiary
  45.                    are defined as electric currents that alternate at a frequency other than 60 Hz
    Harmonics
  46. True/False

    Tertiary windings also furnish a convenient means of connecting
    synchronous condensers to the transmission system, thus eliminating the need of a separate transformer for this purpose
    True
  47. When transformers are connected delta the line current will be 1.732 times the phase current and the          voltage will be the same as the            voltage
    line, phase
  48. When transformers are connected wye, the line voltage will be 1.732 times the phase voltage and the             current will be the same as the              current
    line, phase
  49. Regarding a Closed Delta circuit, The secondary phase wire farthest removed from the grounded neutral is called the 
                         
    "power leg" (N to a)
  50. True/False

    Regarding a Closed Delta circuit, The voltage from the power leg to ground is approximately 208 volts. The voltage from phase to phase is 220 volts.
    False - 240
  51. The use of two single phase transformers
    Open Delta
  52. Pros and Cons of Open Delta
    • The initial cost is reduced because one less transformer is needed
    • only 58% of the power of an equivalent closed delta arrangement.
  53. True/False

    An opened delta connection can not be used if one transformer in a closed delta system fails.
    False
  54. True/False

    In a three-phase circuit, the phase to ground voltage times the square root of 3 equals the line to line voltage
    True
  55. True/False

    The secondary three-phase voltage can be used for either three-phase load or stepped down to supply 120/240 volts.
    True
  56.                   are used to control the flow of power between parallel circuits emanating from the station.
    Phase-shifting banks
  57. Direction of current flow in a closed circuit
    Polarity
  58.                   are used to transform a constant potential system to a constant current system. Street light circuits, connected in series, require a constant current
    Constant current transformers
  59.                   scale down values of current and voltage for use by meters and relays.
    Instrument transformers
  60. Instrument transformers used to step the voltage down
    potential transformers
  61. Instrument transformers used to step the current down
    current transformers
  62. Provide low voltage power for the stations internal operating needs and provide single phase power for the lighting circuits
    and receptacles
    Station Service Transformers
  63. Continually evaluate the combustible gas content of
    the insulating oil.
    Hydran Analyzers
  64. True/False

    The Hydran Analyzer reads:

    100% of the Hydrogen present
    15% of the Carbon Monoxide present
    8% of the Acetylene present
    1% of the Ethylene present
    True
Author
Benjammincash
ID
354801
Card Set
7.4
Description
B3 7.4
Updated