OO-2

  1. True/False

    Electric Trouble Dispatchers (ETDs) have jurisdiction over parts of Feeder primary circuits that can be disconnected without any switching in a DS.
    True
  2. Electric Station/Steam Plant Operators, Electric Trouble Dispatchers, Electric Station Maintenance (ESM) Electrical Mechanics, Line Patrol Mechanics are considered....
    Field Representatives
  3. If the Work Authority is to be released and the equipment is unusable, the equipment shall be declared                        until the work can be resumed under an appropriate Work Authority
    Not Available For Service
  4.                  is a Work Authority requiring the specified circuit or equipment to remain Disconnected and/or Isolated from specified sources of hazardous energy until the                 is released
    Clearance , clearance
  5. An               is a Work Authority allowing specified work to be done on specified circuits or equipment, under specified conditions
    Ok To
  6. A Work Authority granting temporary operational control to either, a Field Representative, or Facility Field Representative (in name of an Electric Station) allowing agreed-upon switching, working, and restoring of specified equipment
    Switch, work, and restore
  7. True/False

    A SWR can be issued on any equipment that crosses an operational boundary (e.g., lines, Feeders, transformer banks with Switchgear that are located in a different Electric Station, etc.).
    False
  8. True/False

    While Diagnostic Test Potential (DTP) is applied, the MAD for the applied test potential is granted an exception.
    False
  9. True/False

    When a Work Authority needs to be released, but the Authorized Person holding the Work Authority is unavailable, the Authorized Person's supervisor may NOT release the Work Authority on the Authorized Person’s behalf
    False
  10. True/False

    All associated switching and operations on DTOs outside the DSs are controlled by the ETB
    True
  11. True/False

    Feeder Streetlight circuits, commonly referred to as Downtown Ornamentals (DTOs) are for streetlight load exclusively
    True
  12. True/False

    Authorized Persons desiring to perform tests or work on these streetlight circuits are responsible for disconnecting these circuits and making their own single point Clearance(s).
    True
  13. True/False

    An Ok To Work Hot is generally issued on circuits or equipment when relays are normal
    True
  14. True/False

    An Ok To Work Hot and an Ok To Block Relays may exist simultaneously on the same circuit or piece of equipment
    False
  15. True/False

    The issuing and releasing of a Clearance on a circuit while an Ok To Work Hot remains in effect is permitted
    True
  16. Shall be performed to identify and document the hazards and control methods required (e.g., engineering controls, administrative controls, PPE, etc.) to protect workers from job specific hazards.
    Job Hazard Analysis
  17. True/False

    No Work Authority shall be issued that will either, violate an existing Work Authority, or create an unnecessary hazard
    True
  18. If the Work Authority is to be released and the equipment is unusable, the equipment shall be declared                     until the work can be resumed under an appropriate Work Authority
    Not available for service
  19. A                is a Work Authority requiring the specified circuit or equipment to remain Disconnected and/or Isolated from specified sources of hazardous energy until the                 is released
    Clearance, clearance
  20. An                  is a Work Authority allowing specified work to be done on specified circuits or equipment, under specified conditions.
    Ok To
  21.                     is a Work Authority granting temporary operational control to either, a Field Representative, or Facility Field Representative (in name of an Electric Station) allowing agreed-upon switching, working, and restoring of specified equipment
    Switch, Work, and Restore (SWR)
  22. Feeders supplied from an IS or a pole top DS are under what jurisdiction
    ETB
  23.                  is required for any work that may affect the reliability, capacity, capability, availability, or response rate of the Power System or any component of System Equipment
    Work Authority
  24. True/False

    Authorized personnel from Distribution, Construction and
    Maintenance (DCM) and Electric Trouble Section (ETS) are
    permitted to work on or within the MAD of energized overhead field circuits or equipment operating at less than 7.5kV which are located outside the Operational Responsibility of an Electric Station without obtaining a Work Authority.
    True
  25. When is equipment declared NOT AVAILABLE FOR SERVICE
    Work Authority is to be released and the equipment is unusable
  26. True/False

    A SWR shall not be issued on any equipment that crosses an operational boundary
    True
  27. True/False

    While Diagnostic Test Potential is applied, the MAD for the applied test potential shall be observed
    True
  28. True/False

    An Ok To Work Hot is generally issued on circuits or equipment when relays are normal
    True
  29. An                   is a Work Authority issued when it is required to apply an excess of 50 Volts to circuits or equipment
    Ok To Apply Foreign Potential
  30. A Work Authority granted only for work associated with locating faults
    Ok To Apply Foreign Potential
  31. True/False

    An Ok To Apply Foreign Potential requires the circuits and equipment be Disconnected
    True
  32. True/False

    In reference to a DTA, when the equipment leads (or equivalents) have been removed, Static Discharge Wires may be used in lieu of PPGs
    True
Author
Benjammincash
ID
353965
Card Set
OO-2
Description
Working On or Near High Voltage Equipment
Updated