(EDG START SEQ) - What happens on a EDG start at 0 RPM
Cranking cycle timer initiate
SACS cooling water valve opens
Low Air start pressure alarms lockout
(EDG START SEQ) - What happens on a EDG start at 95 RPM
Starting air shutoff
(EDG START SEQ) - What happens on a EDG start at >125 RPM
Starting air shutoff (redundant) 2nd
LO Keep Warm heater shutdown
JW Keepwarm pumps and heaters shutdown
Generator Space heater shutdown
Cranking timers de-energized
Engine run timer starts
“Diesel Running Not Loaded” light energized
Exciter field flash circuit activated
Low starting air low pressure alarm re-activated
Motor driven fuel oil pump armed
Motor driven rocker arm prelube pump armed
D/G Room Recirc fan armed
JW &LO Hi Temp alarms disabled
(EDG START SEQ) - What happens on a EDG start at >365 RPM
Starting air shutoff 3rd Signal
Field flash (again)
Low Lube oil pressure trip enabled (indication after 7 sec TD)
(EDG START SEQ) - What is the EDG Ready to load permissive?
>3950VA AND >57hrz