EDG start seq

  1. (EDG START SEQ) - What happens on a EDG start at 0 RPM
    • Cranking cycle timer initiate
    • SACS cooling water valve opens
    • Low Air start pressure alarms lockout
  2. (EDG START SEQ) - What happens on a EDG start at 95 RPM
    Starting air shutoff
  3. (EDG START SEQ) - What happens on a EDG start at >125 RPM
    • Starting air shutoff (redundant) 2nd
    • LO Keep Warm heater shutdown
    • JW Keepwarm pumps and heaters shutdown
    • Generator Space heater shutdown
    • Cranking timers de-energized
    • Engine run timer starts
    • “Diesel Running Not Loaded” light energized
    • Exciter field flash circuit activated
    • Low starting air low pressure alarm re-activated
    • Motor driven fuel oil pump armed
    • Motor driven rocker arm prelube pump armed
    • D/G Room Recirc fan armed
    • JW &LO Hi Temp alarms disabled
  4. (EDG START SEQ) - What happens on a EDG start at >365 RPM
    • Starting air shutoff 3rd Signal
    • Field flash (again)
    • Low Lube oil pressure trip enabled (indication after 7 sec TD)
  5. (EDG START SEQ) - What is the EDG Ready to load permissive?
    >3950VA AND >57hrz