(SEQUENCER) - What happens during a LOCA at T=19?
- "FRVS RECIRC (A-D)
- FRVS VENT (A,B)"
-
(SEQUENCER) - What happens during a LOCA at T=55?
SSW PUMPS
-
(SEQUENCER) - What happens during a LOCA at T=70?
CERS (A,B)407
-
(SEQUENCER) - What happens during a LOCA at T=95?
EDG RECIRC FANS (AUTO) (412)
-
(SEQUENCER) - What happens during a LOP at T=13?
- "DRYWELL FANS
- 9530A1,A3 – B1,B3 – (X)
- (CH WTR VLVS)"
-
(SEQUENCER) - What happens during a LOP at T=45?
SACS PUMPS
-
(SEQUENCER) - What happens during a LOP at T=65?
- "SWGR ROOM COOLERS (401)
- AP400, BP400"
-
(SEQUENCER) - What happens during a LOP at T=80?
1E PNL RM FANS (A,B)408
-
(SEQUENCER) - What happens during a LOP at T=0?
RHR (A-D)
-
(SEQUENCER) - During a LOCA, what is the start time of FRVS VENT (A,B)
T=19
-
(SEQUENCER) - During a LOCA, what is the start time of CRS (403)
T=30
-
(SEQUENCER) - During a LOCA, what is the start time of SACS PUMPS
T=45
-
(SEQUENCER) - During a LOCA, what is the start time of CABE (410)
T=60
-
(SEQUENCER) - During a LOCA, what is the start time of CERS (A,B)407
T=70
-
(SEQUENCER) - During a LOCA, what is the start time of EDG RECIRC FANS (AUTO) (412)
T=95
-
(SEQUENCER) - During a LOCA, what is the start time of CORE SPRAY (A-D)
T=5
-
(SEQUENCER) - During a LOP, what is the start time of EDG RECIRC FANS (AULD) (412)
T=30
-
(SEQUENCER) - During a LOP, what is the start time of CREF (400)
T=30
-
(SEQUENCER) - During a LOP, what is the start time of (A,B)K400
T=60
-
(SEQUENCER) - During a LOP, what is the start time of AP400, BP400
T=65
-
(SEQUENCER) - During a LOP, what is the start time of 1E PNL RM FANS (A,B)408
T=80
-
(SEQUENCER) - During a LOP, what is the start time of RHR (A-D)
T=0
-
(SEQUENCER) - What happens during a LOCA at T=30?
- "FRVS RECIRC (E,F)
- EDG RECIRC FANS (AULD) (412)
- CRS, CRRA, CREF
- (403), (415), (400)"
-
(SEQUENCER) - What happens during a LOCA at T=60?
-
(SEQUENCER) - What happens during a LOCA at T=75?
(A,B)K403, (A,B)P414 (BOTH TSC)
-
(SEQUENCER) - What happens during a LOCA at T=0?
RHR (A,B)
-
(SEQUENCER) - What happens during a LOP at T=19?
RBVS
-
(SEQUENCER) - What happens during a LOP at T=55?
SSW PUMPS
-
(SEQUENCER) - What happens during a LOP at T=70?
CERS (A,B)407
-
(SEQUENCER) - What happens during a LOP at T=85?
- "RACS(A,B)
- 9530A2,A4 – B2,B4 – (0)
- (RACS WTR VLVS)"
-
(SEQUENCER) - What happens during a LOP at T=10?
CORE SPRAY (A-D)
-
(SEQUENCER) - During a LOCA, what is the start time of FRVS RECIRC (E,F)
T=30
-
(SEQUENCER) - During a LOCA, what is the start time of CRRA (415)
T=30
-
(SEQUENCER) - During a LOCA, what is the start time of SSW PUMPS
T=55
-
(SEQUENCER) - During a LOCA, what is the start time of SWGR ROOM COOLERS (401)
T=65
-
(SEQUENCER) - During a LOCA, what is the start time of (A,B)K403, (A,B)P414 (BOTH TSC)
T=75
-
(SEQUENCER) - During a LOCA, what is the start time of RHR (A,B)
T=0
-
(SEQUENCER) - During a LOP, what is the start time of DRYWELL FANS and the CLOSE of 9530A1,A3 – B1,B3, (CH WTR VLVS)
T=13
-
(SEQUENCER) - During a LOP, what is the start time of CRS (403)
T=30
-
(SEQUENCER) - During a LOP, what is the start time of SACS PUMPS
T=45
-
(SEQUENCER) - During a LOP, what is the start time of CABE (410)
T=60
-
(SEQUENCER) - During a LOP, what is the start time of CERS (A,B)407
T=70
-
(SEQUENCER) - During a LOP, what is the start time of RACS(A,B) and the OPEN of 9530A2,A4 – B2,B4, (RACS WTR VLVS)
T=85
-
(SEQUENCER) - During a LOP, what is the start time of CORE SPRAY (A-D)
T=10
-
(SEQUENCER) - What happens during a LOCA at T=45?
SACS PUMPS
-
(SEQUENCER) - What happens during a LOCA at T=65?
- "SWGR ROOM COOLERS (401)
- AP400, BP400"
-
(SEQUENCER) - What happens during a LOCA at T=80?
1E PNL RM FANS (A,B)408
-
(SEQUENCER) - What happens during a LOCA at T=5?
- "RHR (C,D)
- CORE SPRAY (A-D)"
-
(SEQUENCER) - What happens during a LOP at T=30?
- "EDG RECIRC FANS (AULD) (412)
- CRS, CRRA, CREF
- (403), (415), (400)"
-
(SEQUENCER) - What happens during a LOP at T=60?
-
(SEQUENCER) - What happens during a LOP at T=75?
(A,B)K403, (A,B)P414 (BOTH TSC)
-
(SEQUENCER) - What happens during a LOP at T=95?
EDG RECIRC FANS (AUTO) (412)
-
(SEQUENCER) - During a LOCA, what is the start time of FRVS RECIRC (A-D)
T=19
-
(SEQUENCER) - During a LOCA, what is the start time of EDG RECIRC FANS (AULD) (412)
T=30
-
(SEQUENCER) - During a LOCA, what is the start time of CREF (400)
T=30
-
(SEQUENCER) - During a LOCA, what is the start time of (A,B)K400
T=60
-
(SEQUENCER) - During a LOCA, what is the start time of AP400, BP400
T=65
-
(SEQUENCER) - During a LOCA, what is the start time of 1E PNL RM FANS (A,B)408
T=80
-
(SEQUENCER) - During a LOCA, what is the start time of RHR (C,D)
T=5
-
(SEQUENCER) - During a LOP, what is the start time of RBVS
T=19
-
(SEQUENCER) - During a LOP, what is the start time of CRRA (415)
T=30
-
(SEQUENCER) - During a LOP, what is the start time of SSW PUMPS
T=55
-
(SEQUENCER) - During a LOP, what is the start time of SWGR ROOM COOLERS (401)
T=65
-
(SEQUENCER) - During a LOP, what is the start time of (A,B)K403, (A,B)P414 (BOTH TSC)
T=75
-
(SEQUENCER) - During a LOP, what is the start time of EDG RECIRC FANS (AUTO) (412)
T=95
|
|