What is the main purpose of the fire department pumper
To provide water at an adequate pressure
-
What is the minimum pump capacity for pumpers
750 GPM
-
What is the required vision for the fire department
20/40 with contact lenses or spectacles
-
Any fire fighter Canidate be rejected with a hearing loss of what
40 dB are more
-
Industrial fire pumpers frequently have pump capacities in excess of what
2000gpm
-
Most large scale industrial foam pumpers are equipped with fire pumps that range in what capacity
1000 to 3000 gpm
-
Most Industrial foam pumpers have a large foam concentrate tank on board these tanks range from
500 and1500 gallons
-
Most common size foam tanks for municipal fire apparatus are
20 to 100 gallons
-
Elevating water device typically range in what heights
50 to 75 feet
-
Mini pumper’s are most often mounted on pickup chassis what is there pump GPM
500 to 1000gpm
-
Midi pumpers are built on chassis usually over 12,000 pounds What size pump are midi pumpers equipped with
1000 gpm
-
According to NF PA 1901 the apparatus must carry at least how many gallons to be considered a mobile water supply apparatus
1000 gallons
-
Single rear axle vehicles are limited to what size tank
1500 gallons Max
-
When tank capacities are greater than 1500 gallons what is required
Tandem rear axles tri axles or tractor trailer
-
Majority of wildland apparatus have pump capacities and water tank sizes of less than what
500gpm and 500 gallons
-
Booster tanks for wild land apparatus vary from what
20 to 1000 gallons
-
Rescue apparatus with a fire pump have a capacity of what GPM and tanksize of what gallons or less
500 GPM or less and 500 gallons or less
-
What is a inverter
Converts vehicles 12 or 24 V DC current to a 110 or 220
-
What are the advantages of an inverter and what is it capable of providing
Fuel efficient and noise 1500 W or more
-
What is the minimum pump capacity for an aerial
250 GPM
-
What is the minimum pump capacity for a quint
750gpm
-
Ladder tenders do not exceed how many gallons and do not produce more than how many GPM
300 gallons and 300 GPM
-
Some mobile water Supply apparatus can discharge water up to what
1750 GPM
-
Fireboats have been built to deliver as much as how many GPM and is individual master stream turret can discharge how many GPM
26000 gpm 2000 to 3000 gpm
-
How many watts do portable generators usually supply
5000 W
-
Vehicle mounted generators can supply how many watts
12,000 W
-
Rescue vehicles commonly have larger generators with capacities of what
50,000 W
-
Lighting equipment can be divided into what to categories
Portable fixed
-
Portable lights Generally range from what
300 to 1000 W
-
The most common size of cable for wiring is
12 gauge three wire type
-
You shouldn’t exceed how many feet of hydraulic hose for hydraulic tools
Hundred feet
-
What is the best way to apply water to apparatus
Garden hose without a nozzle less than 1 foot away
-
When does the driver operator inspection being on a vehicle
While approaching the vehicle
-
Keeping apparatus in a state of usefulness or readiness
Maintenance
-
Restore or replace that which has become in operable
Repair
-
During the first six months after an apparatus is received it should be washed with what
Coldwater to hard in the paint
-
Wax or polish should not be applied until the pain is at least how old
6 months
-
In general steering wheel play should not be more than what
10° in either direction
-
The parking break should hold the apparatus and place on a grade of what
20%
-
Apparatus equipped with airbrakes should build to a sufficient level to allow vehicle operation within how many seconds
60
-
Apparatus with airbrakes are to be equipped with an air pressure protection valve that prevents the airhorns from being operated when the pressure is below what
80 psi
-
The starter control should be operated in intervals of no more than what with a rest of what if it doesn’t start
30 seconds and 60 seconds
-
Snow chains tend to lose their effectiveness in snow that is deeper than what
8 inches or when the vehicle is moving at a very slow speed or in reverse
-
When more than one emergency vehicle is responding along the same route unit should travel at least how far apart
300 to 500 feet
-
Serpentine test
At least three markers 30 to 38 feet apart backwards first then forward
-
Missing clearance test consist of a lane _____ feet long and arrows from_____ at a point of___ ft past last section you must stop within ____ inches of finish line
75 ft -9ft 6in to 8ft 2in- 50ft- 6in
-
Ali dock exercise simulates what
Backing down an alley that is 40 foot wide into a dock that is 12’ x 20’
-
What is the confined space turnaround size
50 foot wide and 100 feet long
-
For a road test you must drive at least how far on a business trip
1 mile
-
What is the total stopping distance
Reaction distance plus braking distance
-
What is reaction distance
The distance traveled from the time you realize you need to stop to when you touch the brake pedal
-
Braking distance
Distance from one traveler applies pressure on break pedal to stop
-
What is the most likely place of collision involving emergency vehicles
Intersections
-
How long should engine be allowed to cool
3 to 5 minutes
-
A vehicle going 40 miles an hour Can project how far in front the vehicle
300 feet
-
A vehicle going 60 mph can only project how far
12 feet
-
How big is the collapse zone
One and a half times the height of the building
-
Where is the safest place for collapse on the building
Corner of building
-
If the building is less than 5 stories where do you place the truck
Truck is on outside and engine on the inside
-
If the building is more than five stories where do you place the truck
The truck is placed inside and the engine on the outside
-
When pumpers are connected intake to intake to supply water off of 1 hydrant
Dual pumping
-
When 2 pumpers may be positioned as much as 300 feet apart and one pumps to the other to boost the pressure
Tandem pumping
-
A natural or man-made Barrier that will prevent the fire from spreading around and in circling the engine and crew
Anchor point
-
Level one staging
And emergency response when two or more companies are dispatched
-
Level two staging
With numerous emergency vehicles will be responding to the same incident incidents that require a mutual aid or that result multiple alarms
-
Who will become the staging area manager
The company officer on the first company to arrive at the staging area
-
Companies and staging must be ready to respond within how soon
Three minutes
-
What is decontamination usually take place
Warm zone
-
How do you park a command vehicle
Outside of danger zone where you can see two sides of structure
-
How many cylinders to Cascade systems usually have
4-12
-
Engine driven appliances that taking atmosphere air purifier and compress it for SCba refill equipped with hose reels
Breathing air compressor
-
Two primary types of EMS vehicles that respond to fires
Rapid response units non-transport and ambulances transport
-
What is a caution on tandem pumping
May pump water at greater pressure’s than hose can withstand
-
When connecting to a front or rear intake how do you position apparatus
45degree angle
-
Easiest way to ensure maximum water flow
Remove kinks
-
What is a good way to minimize kinks
Put 2 twists in hose
-
Pumpers provisioning water to elevated streams should park where
As close to aerial as possible to reduce friction loss
-
The boundary between wild land and structural is often referred to as
Wild land urban interface
-
Most common used extinguishing agent
Water
-
The primary way water extinguishes fire is
By cooling
-
What governs the heat absorbing ability of water ____and ____
Specific heat and Latent heat of vaporization
-
The speed with which water absorbs heat increases in proportion to the water surface exposed to the heat
Exposed surface area
-
Water expands how many times when converted to steam
1700 times
-
Tendency of a liquid to possess internal resistance to flow
Viscosity
-
At sea level atmosphere exerts a pressure of
14.7 psi
-
What are the three means of moving water in a system
Direct pumping system gravity system combination system
-
The average of total water used in a water distribution system over the period of one year
Average daily consumption
-
Maximum total amount of water used during on any 24 hour interval within three years
Maximum daily consumption
-
Maximum amount of water used in a one hour interval over the course of a day
Peak hourly consumption
-
The height of a water supply above the discharge orifice is considered
Head pressure
-
A measure of heat absorbing capacity of a substance
Specific heat
-
Amounts of heat transfer or measured in
British thermal units Or Jules
-
Stored potential energy available to force water through pipe hose and adapters is what
Static pressure
-
Pressure found in a water distribution system during normal consumption demands
Normal operating pressure
-
Part of the total available pressure not used to overcome friction loss or gravity all forcing water through hose or pipes
Residual pressure
-
The forward velocity pressure at a discharge opening well water is flowing
Low pressure
-
The density of liquids in relation to water is known as
Specific gravity
-
When a fire hydrant receives water from two or more directions it’s called
Circulating feed or Looped line
-
A water grid system contains what three components
Primary feeders secondary feeders distributors
-
Heat required to bring 1 pound of water up 1 degree
Btu
-
The quantity of heat absorbed by a substance when it changes from a liquid to a vapor
Latent heat of vaporization
-
Each pound of water requires approximately____ btu to convert into steam
970 btu
-
High pressure fog nozzles operate at pressures up to What? Most commonly used for what? How much gpm?
- 800 psi
- Fighting wildland fires
- 8 to 15 G PM
-
Detachable ladder pipes are most common on? Supplied by what
- Light duty aerial ladders
- 3 in hose tied to ladder
-
What are the basic categories of master stream devices
Monitor turret pipe deluge set elevated master Stream
-
The most common variable flow nozzle in use
Automatic nozzles or constant pressure nozzles
-
Chimney nozzle pressure and gpm
100psi 1.5 to 3gpm
-
What is designed to flow a specific amount of water at a specific nozzle discharge pressure on all stream patterns
Constant flow nasal
-
What is the maximum amount of water that can flow through a hand line safely
350gpm
-
Three basic types of fire streams
Solid fog and broken
-
A fire hydrant that receives water from only One Direction
Dead end hydrant
-
What size supply pipe is in residential areas
6 inches
-
In business and industrial district what is the minimum water main size
8 in
-
On principle streets and long Manes not cross connected at frequent intervals what is the recommended main size
12 in
-
How many GPM does a piercing nozzle deliver
100gpm
-
Accurate method for determining pressure loss in any particular hoselay
Measuring the pressure at both ends of the hose and subtracting the difference
-
Each discharge equipped with a flow meter has a digital readout display married how close within the valve control
6 inches
-
Two basic types of flow meter sensors
Paddlewheel and spring probe
-
Flow meters should be accurate within what
+ or- 3%
-
What are the two types of hydraulic calculators
Manual or mechanical and electronic
-
What was the earliest pumps used in the fire service
Hand operated
-
Two types of positive displacement pumps
Rotary and piston pump
-
What can positive displacement pumps do that centrifugal pumps cannot
Pump air
-
The simplest of all fire apparatus pumps
Rotary pump
-
What type of metal is for gears to prevent damage in Rotary vane pumps
Bronze
-
What type of metal is used for the casing on a rotary gear pumps
A strong alloy like cast iron
-
The most common type of pump used to prime centrifugal pumps
Rotary vane pump
-
A non-positive displacement pump because it does not pump a definite amount of water with each revolution
Centrifugal pump
-
What to parts does the centrifugal pump consist of
Impeller and casing
-
The impeller on a centrifugal pump rotates how fast
2000 to 4000rpm
-
The larger the eye on centrifugal pump
The greater the flow
-
The process of switching between pressure and volume is sometimes referred to as
Change over
-
Put manufacturers specify that the pump may remain in pressure until is necessary to flow what
2/3 of the rated flow capacity
-
Rear skid mount assemblies pumping maximum GPM is
500gpm
-
What pumps offer the maximum amount of flexibility
Auxiliary engine driven pumps
-
What type of pumps are commonly used at industrial and fire training facilities
Trailer mounted pumps
-
What is a disadvantage of front mount pumps
More susceptible to freezing and can obstruct airflow and cause engine to overheat
-
What is the most common type of pump used in the fire service
Midship pumps
-
What are the primary components of the piping systems
Intake piping, discharge Piping, pump drains and valves
-
Most piping systems are constructed of
Cast iron brass stainless steel or galvanize steel
-
Apparatus with water tank that is less than 1000 gallons in size have a tank fill line that is at least how big
1 in
-
Apparatus with the tanks that are 1000 gallon or larger must have at least how big tank fill line
2 in
-
All valves should be designed so they are easily operable at pressures up to what
250 psi
-
PReconnected attack lines must be supplied by at least how big of piping
2 in
-
All fire apparatus with her rated pump capacity of 750 GPM or greater must be equipped with what
At least two 2 1/2 inch discharges
-
Pumps that are rated less than 750 GPM are only required to have what
One 2 1/2 inch discharge
-
The most common type of valve
Ball type valve
-
The most common actuators for ball type valves are
Push pull handles or quarter turn handles
-
All valves on intakes or discharges that are 3 inches or greater will be equipped with what
Slow acting valve controls
-
The pressure control device on fire apparatus pumping must
Operate within 3 to 10 seconds after the discharge pressure rises and not allow the pressure to exceed 30psi above set level
-
One of the most common types of relief valves
Spring controlled pilot valve
-
It is recommended that intake relief valves decide to open when the intake pressure rises more than ____above the desired operating pressure
10psi
-
What are the three types of primer
Positive displacement exhaust and vacuum
-
Most modern fire apparatus use what type of primer
Positive displacement primer
-
The simplest type of primer
Vacuum primer
-
Master intake and discharge gauges are usually calibrated to what
600psi
-
The most common throttle used on the pump operators panel
Vernier
-
Two types of auxiliary coolers, we found an older apparatus
Marine and immersion type
-
What are gate or butterfly valves most common on
Large diameter discharges and intakes
-
Pumpers with a capacity of 500 or below should be capable of flying how much GPM from booster tank
250 GPM
-
Pumpers greater than 500 capacity should be able to flow how much gpm
At least 500 GPM
-
On discharge piping all valves should be easily operable at pressures up to
250 psi
-
What is the main fire pump on modern apparatus
Centrifugal pumps
-
The piping system must be able to withstand a hydrostatic test of what
500 psi
-
What is the most common type of pump used to prime centrifugal pumps
Rotary vein pump
-
What are the two basic pressurized water supply sources that maybe used to supply a fire pump
Hydrant or supply hose from another engine
-
When using 2 1/2 or 3 inch supply lines to the pumper it is recommended that the Lines not be longer than what
300 feet
-
The maximum amount of vacuum that most pumps develop is
22 inches of mercury
-
How much water is supposed to be around stainer when drafting
2ft around all sides
-
Low level strainers are designed to draft to a depth of how far from the bottom
1- 2 inches
-
A pumper in good condition can lift water how far
24 feet
-
At 20 feet of lift the amount of water that can be supplied is only
60% of the rated capacity of the pump
-
What are the most common sources of air leaks on pumps
Open drains or valves
-
1000 GPM pumper supply how many sprinklers
50
-
Do not operate a primer for more than how long when it is dry
10 seconds
-
-
Orange hydrant gpm
500 to 999
-
Green hydrant gpm
1000 to 1499
-
Blue hydrant gpm
1500 and greater
-
What is the most demanding type of pump operation
Pumping from draft
-
Two stage pumpers should be in what stage while supplying sprinklers or stand pipe
Volume
-
In 2 stage pumps which stage is the best to prime in
Volume
-
The height of a fire pump above the surface of the water source
Lift
-
The maximum height which any amount of water may be raised through a hard intake hose to the pump
Maximum lift
-
The height a column of water maybe lifted insufficient quantity to provide a reliable fire flow
Dependable lift
-
Upon about the size of the US football field and 1 foot deep with supply thousand GPM pump or for how long
Five hours
-
Floating strainers allow safe drafting from water as low as
1 ft deep
-
What are the two primary static water sources
Natural and man-made
-
Agricultural irrigation systems can flow up to what
1000 GPM
-
What is usually the maximum lift in a hard intake hose
25 feet
-
What is another name for relay pumper
In line pumper
-
The engine with his largest pump capacity is placed where in relay operation
At the beginning of the relay operation (the source pumper)
-
Source pumper
Supply pumper
-
Intake pressure relief valve also called
Relay relief valve
-
Relay operations should be shut down where first
The fire scene
-
What are the three major components of water shuttle operation
The fill site shuttle route the dumpsite
-
The primary way to increase efficiency of water shuttle operations are
Decrease the amount of time required to fill in the amount of time to unload the tenders
-
Tenders with 750 GPM or larger fire pumps are often called
Pumper tenders
-
The two primary type of the large tank discharges on water tenders are
Gravity dumps and jet assisted dumps
-
The most desirable route for water shuttles
Circular route
-
Tenders should be able to dump at a minimum average flow rate of 1000 GPM for how long
The first 90% of the tank
-
The most common type of portable water tank is
The folding type
-
When testing hose the couplings should not move how far away from the house
3/8 in
-
All gauges must have been calibrated within how many days of testing
60
-
Hydrostatic test for pump’s perform how long
250 psi for 3 min
-
Class B fuels are divided into two categories
Hydrocarbons and polar solvents
-
What are hydrocarbons
Fuel’s such as crude oil gas benzene naphtha kerosene that float on water
-
What are polar solvents
Alcohol acetone lacquer thinner key tones and esters fuel that mix well with water
-
What are the four basic methods foam may be proportioned
Induction injection batch mixing pre-mixing
-
Foam concentrate tanks on municipal pumpers range from what
20 to 200 gallons
-
Foam pumpers and tenders may carry how much concentrate
8000 gallons
-
What is the shelf life of class a foam (synthetic foam)
20 years
-
Class B foam concentrates are manufactured from
Synthetic or protein base
-
What is the shelf life of protein-based foams
10 years
-
What is the most commonly used foam today
Afff
-
What is the simplest and most common foam proportioning devices in use today
Portable foam proportioners
-
What are the three common types of portable foam proportioner’s
In-line foam educters foam nozzle eductors and self ededucting master stream nozzles
-
Self educting Master stream foam nozzles are used in excess of 350 GPM with capabilities of up to what
14,000 GPM
-
A jet ratio controller maybe used to supply foam how far away
3000 feet
-
Most common type of built in proportioners installed mobile fire apparatus today
Around the pump proportioner
-
The simplest means a proportioning foam
Batch mixing
-
Ifsta Defines a hand line nozzle is any nozzle that one to three firefighters can’t safely handle that flows less than what
350 gpm
-
The two basic types of medium and high expansion foam generators are
The water aspirating type and the mechanical blower
-
What is the most basic type of foam proportion are used in the fire service (test)***
In-line foam eductor
-
To ensure sufficient water what should run from the source of the supply to the high-risk and industrial districts of a community
Two or more primary feeders
-
In residential areas the recommended size for a fire hydrant supply mains is whatsize in diameter and there should be 8 inch crossconnect a mains at intervals of not more than how many feet
6 in mains crossconnect every 600 ft
-
What is the minimum recommended size of water main in business and industrial district that crossconnect every how many feet
8 in main that cross connect every 600 ft
-
What size water mains may be used on principle streets and tlong mains not cross connected in frequent intervals
12 in
-
Valve for water systems are divided into what types
Indicating and non-indicating
-
The simplest type of primer
Vacuum primer
-
All fire pumps are required to pump there capacity at what
10ft of lift
-
Intake pressure relief valves are also called
Relay relief valves
-
What are the most common actuators for Ball type valves
Push poll handles or quarter turn handles
-
Most constant flow nozzles are intended to be operated had a pressure of what
100 psi
-
Screw thread for fire service specified by nfpa 1963
National standard thread
-
Most foam concentrates are intended to be mixed with
94 to 99% of water
-
The only type of nozzle that can be used with protein and flour protein concentrates
air aspirating foam nozzle
-
The 2 basic types of medium and high expansion foam generators
The water aspirating type and mechanical blower
-
Driver operators a fire apparatus regulated By
State or provincial laws city ordinances and SOP’s
-
ARFF apparatus are divided into what classifications
- Major firefighting vehicles
- Rapid intervention vehicles
- Combined agent vehicles
-
What are fire boats used for
I’m putting large mass for streams and providing additional water for onshore firefighting operations
-
Hearing protection should be worn when exposed to noise in excess of
90 decibels
-
What are the three exceptions to not wearing a seatbelt
- Providing patient care
- loading hose
- performing training on tiller
-
Vehicles with airbrakes have how long of a delay
.4 seconds
-
What is the first type of auxiliary braking system
Front brake limiting valve type
-
Studies have shown that people respond better to sirens that do what
Change pitch
-
What are the two most common functions of wildland apparatus
Structural protection and direct attack on fire
-
How much of calls or medical calls
60%
-
The measure of heat absorbing capacity of a substance
Specific heat
-
The two most common indicator valves are
Post indicator valve used for private water supply and outside screw and yoke valve used for sprinklers
-
Solid stream and the nozzles are operated at what
50 psi
-
Solid stream master stream devices are operated at what
80psi
-
The line Bounding a rounded surface the outward boundary of an object distinguished from his internal regions
Periphery
-
They turning or state of being turned, bending, deviation
Deflection
-
To strike or – about or against clashing with a sharp collision come together with force
Impinge
-
Any fire stream it is too large to be controlled without mechanical aid
Master stream
-
The power system to operate a master stream maybe
Electric hydraulic or pneumatic
-
The practical working limits for velocity Fire streams are within what
60 to 120 ft per second
-
Hose layouts can be divided into what two categories
Simple and complex
-
Discharges are usually equipped with what type of valve
Locking ball valve
-
What is the buildings first line of defense against a controlled fire
Fixed fire protection systems
-
What are the 2 basic designs for relay pumping operations
Maximum distance relay and Constant pressure relay
-
What are the two type of manufacturer tests
Road and hydrostatic test
-
NF PA 1901 requires breaking test of apparatus to be brought to a complete stop on the speed of what within how many feet
20 mph 35 ft
-
What is the first element in learning to drive safely
Safety conscious attitude
-
Some departments train drivers to look how far ahead on city streets and highways
- 12 seconds on city streets
- 20 seconds on highways
-
The apparatus it’s self is what
Potential exposure
-
How far do preemptors work
100 feet to 1/2 mile
-
Large debris can fall how far from incident? If it cannot be moved what must be done?
- One block
- Cover with salvage tarps
-
What is the preferred type of hose to connect to a hydrant
Large intake soft suction
-
What is a disadvantage to connecting 2 1/2 to Hydant
Limits water
-
Breathing air compressors have what that prevent use of air if it is contaminated
Interlocks
-
Who designates the staging area
Operations section chief
-
When can apparatus only be driven against traffic
If police have closed road
-
What type of pumpers are more safe on the highway incidence
Top mount
-
What are water pipes underground usually made of
Cast-iron, ductile steel, asbestos cement, Steel, plastic, concrete
-
Water curtains are only effective and absorbing what
Convected heat
-
What are cellar nozzles often called
Distributors
-
What is the purpose of fire ground calculations
Discharge appropriate water
-
Most common type of pump packing is made out of what
Rope fibers in bedded with graphite or lead
-
What is a disadvantage of mechanical governors
It lowers discharge pressure on all lines, this doesn’t happen with electronic governors
-
If apparatus uses a vacuum type primer what should happen
Engine RPM should be kept as low as possible
-
Who’s tenders are usually carry how much hose
Mile
-
What are the back bone to any water shuttle operation
Water tenders
-
Today’s class B farms are mixed in proportion of what
1 to 6%
-
If pump test less than 90% operating what must be done
Be taken out of service and fixed or changed the flow rating
-
Test the quality of foam after it has been made
Foam solution refractivity test
-
Used to test quality of synthetic based foams
Foam solution conductivity test
|
|