FEL B

  1. ___________________ shall be located on the front of the extinguisher and shall be clearly visible.




    B) Extinguisher operating instructions
  2. The vapor phase of carbon dioxide shall not be less than ________ percent carbon dioxide.




    A) 99.5%
  3. The premixed agent in liquid-charge-type AFFF and FFFP fire extinguishers shall be replaced at least once every ____________.




    A) 3 Years
  4. True or False: Fire extinguishers shall not be obstructed or obscured from view, except in large rooms and in certain locations where visual obstruction cannot be completely avoided.
    True
  5. True of False: If a wet chemical extinguisher is partially discharged, all remaining wet chemical shall be discarded.
    True
  6. True or False: The system used to rate fire extinguishers on Class B fires (flammable liquids in depth) is not directly applicable to three-dimensional Class B fires
    True
  7. All types of fire extinguishers, except water-types, shall not be installed in areas where the temperatures are outside the range of _____________.




    B) - 40ºF to 120ºF
  8. Where fire extinguishers are installed in closed cabinets that are exposed to elevated temperatures, the cabinets shall be provided with ______________.




    B) screened openings and drains
  9. At the time of maintenance, the tamper seal of a rechargeable fire extinguisher shall not be replaced, unless it shows evidence of tampering.
    • False
    • At the time of maintenance, the tamper seal of a rechargable fire extinguisher shall be removed by operating the pull pin or locking device. After the applicable maintenance procedures are completed, a new tamper seal shall be installed.
  10. When an inspection of any non-rechargeable fire extinguisher containing a Halon agent reveals a deficiency, it shall be removed from service, discharged, and returned to the manufacturer.
    • False
    • When an inspection of any non-rechargable fire extinguisher containing a Halon agent reveals a deficiency, it shall be removed from service, not  discharged, and returned to the manufacturer.
  11. Fire extinguishers and extinguishing agents for the protection of __________ hazards shall be of types approved for use on the specific combustible-metal hazard.




    B) Class D
  12. Pails or drums containing dry powder agents for scoop or shovel application for use on metal fires shall be __________________.




    B) Kept full and covered
  13. Class D fires are _______.




    B) fires in combustible metals, such as magnesium, titanium, zirconium, sodium, lithium, and potassium
  14. Liquefied gas, halogenated agent, and carbon dioxide extinguishers that have been recharged without valve removal do not require a ______________.




    D) "Verification of Service" collar
  15. A fire extinguisher shall have a label, tag, stencil, or similar indicator attached to it providing the following information.




    D) all of the above
  16. Class B fires are _____________.




    B) fires in flammable liquids, combustible liquids, petroleum greases, tars, oils, oil-based paints, solvents, lacquers, alcohols, and flammable gases
  17. The following types of fire extinguishers are considered obsolete and shall be removed from service
    • soda acid
    • vaporizing liquid (such as carbon tetrachloride)
  18. Carbon dioxide is ________________ than air




    B) 1 1/2 times heavier
  19. Fire extinguishers or extinguishing agents (media) shall be located not more than _________ of travel distance from a Class D hazard.
    75 feet
  20. A regulated source of pressure, set no higher than __________ above the operating (service) pressure, shall be used to pressurize fire extinguishers.
    25 psi
  21. Every _____________, pump tank water and pump tank calcium-chloride-based antifreeze types of fire extinguishers shall be recharged with new chemicals or water, as applicable.
    12 Months
  22. Fire extinguishers having a gross weight greater than 40 pounds (except wheeled types) shall be installed so that the top of the fire extinguisher is not more than ______ above the floor.
    3 1/2 ft
  23. Multipurpose dry chemicals shall not be mixed with ______________ dry chemicals.
    alkaline based
  24. Fire extinguishers shall be inspected at approximately ___________ intervals and at more frequent intervals when circumstances require.
    30 days
  25. During annual maintenance of stored-pressure type extinguishers which
    contain a loaded stream agent, the loaded stream agent shall be permitted to be recovered and reused, provided it is subjected to agent analysis in accordance with the manufacturer’s instructions.
    True
  26. Fire extinguishers installed under conditions where they are subject to physical damage (e.g., from impact, vibration, the environment) shall be _________.
    adequately protected
  27. _________ shall keep records of all fire extinguishers inspected, including those found to require corrective action.
    personnel making inspections
  28. _____________ extinguishers do not require a "Verification of Service" collar




    A) cartridge-cylinder operated
  29. _______________ types of fire extinguishers shall not be used for the protection of water-soluble flammable liquids, such as alcohols, acetone, esters, keytones, and so forth, unless specifically referenced on the fire extinguisher nameplate.




    A) AFFF and FFFP
  30. The acronym "FFFP" means _________________.
    film-forming fluoroprotein foam
  31. Fire extinguishers having a gross weight not exceeding 40 pounds shall be installed so that the top of the fire extinguisher is not more than ______ above the floor.




    A) 5ft