NDE - What is the minimum time an examiner should be in a darkened area prior to using a black light for MT & PT exams?
5 minutes.
Reference Sect V: T-676.4.b and T-777.2.b
NDE - What is the time range for final interpretation of a PT exam after developer has been applied?
10-60 minutes.
Reference Sect V: T-676.1
Testing - What is the typical minimum duration for a pressure test?
30 minutes
Reference API 577: 9.11
NDE - What is the minimum time to wait to check for delayed cracking after repairs to SS cladding?
24 hours
Reference API 510: 8.1.6.4.4
NDE - What is the max calibrating interval for an RT densitometer?
90 days
Reference Sect V: T-262.1
Welding - What is the maximum time a welder or welding operator can maintain qualifications for a process without using that process?
6 months
Reference IX: QW322.1.a
NDE - What is the maximum interval for a visual examiner's eye exam?
1 year
Reference API 577: 9.3.1.d
Inspection - What is the maximum interval for an internal inspection if the remaining life is less than 4 years?
Lesser of: 2 years or full life.
Reference API 510: 6.5.1.1
Inspection - What is the maximum interval for an external inspection?
Lesser of: 5 years or internal.
Reference API 510: 6.4.1
Inspection - What is the maximum interval for relief devices in fouling or corrosion service?
5 years
Reference API 510: 6.6.3.2.a
Inspection - What is the maximum interval for an internal or on-stream inspection?
Lesser of: 10 years or 1/2 life
Reference API 510: 6.5.1.1
Inspection - What is the maximum interval for relief devices in non-fouling or non-corrosive service?
10 years
Reference API 510: 6.6.3.2.b
RBI - What is the maximum interval for the RBI reassessment?
10 years
Reference API 510: 6.3.2
Inspection - What minimum remaining life is required when performing an On-stream inspection in lieu of an Internal inspection?
>10 years
Reference API 510: 6.5.2.1.b.2
NDE - What is the maximum calibration interval for MT magnetic yokes?
MT yokes should be calibrated yearly and the magnetizing force should be verified before each use.
Reference Sect V T-762.a and T-761.1a
NDE - When do you need to check the light intensity of a black light used in a MT or PT exam?
Before and after use.
Reference Sect V: T-676.4.e and T-777.2.e