LCS 2 Electrical EOCC

  1. MLSSG
    Loss of Ship Service Generator
  2. Symptoms/Indications: MLSSG (L/O)
    • 1. Loss of Lube Oil Pressure
    • a. Low L/O Pressure alarm sounds (4.5 bar above 1600 rpm)
    • b. Low Lube oil pressure shutdown activates (4 bar above 1600 RPM)
    • c. High Lube Oil Temperature Alarm (105C)
  3. Symptoms/Indications: MLSSG (F/O
    • 2. Loss of Fuel Oil Pressure
    • a. Low F/O pressure alarm sounds (2.5 bar @ 1800 RPM)
    • b. SSDG slows or stops
    • c. F/O service tank low level indicated
    • d. Generator circuit breaker trips without command
  4. MLSSG Possible Effects
    • 1. Loss of SSDG
    • 2. Reduced electrical generator capacity
    • 3. Personnel injury
    • 4. Class BRAVO fire
  5. MLSSG Controlling Actions
    • NOTE: When an alarm condition exists that does not cause an auto E-Stop, proceed as follows:
    • A. RCO report alarm condition to OOD and order CRT to man affected space
    • B. When ordered, CRT man affected space
    • C. CRT report to RCO "Manned & Ready"
    • D. RCO start stdby SSDG and parallel standby SSDG to bus
    • E. RCO open generator breaker for affected SSDG and stop affected SSDG
    • F. RCO report to OOD "Loss of No_ SSDG, No_ SSDG started & paralleled to bus"
  6. MLSSG Immediate Actions
    • WARNING: WHEN FUEL OIL LEAK IS PRESENT PROCEED IMMEDIATELY TO ID NO. MMFOL
    • WARNING: WHEN CLASS BRAVO FIRE IS PRESENT PROCEED IMMEDIATELY TO ID NO. MCBF
    • A.RCO report to OOD "LOSS OF NO_ SSDG"
    • B When required, RCO E-STOP affected SSDG. Ensure generator breaker opens
    • C. RCO ensure stdby SSDG starts
    • D. RCO parallel stdby SSDG to bus
    • E. RCO order CRT to man affected space
    • F. When ordered, CRT man affected space
    • G. CRT report to RCO "Manned & Ready"
    • H. CRT visually inspect for fuel/lube/coolant/seawater leak
    • I. When required, CRT man firefighting equipment and report to RCO "Firefighting equipment manned"
  7. MDGGM
    Ship Service Diesel Generator Governor Malfunction
  8. MDGGM Symptoms/Indications
    • 1. Excessive hunting of governor or fluctuating engine speed
    • 2. Engine fails to respond to load change
    • 3. Generator load imbalance
  9. MDGGM Possible Effects
    • Loss of ship service diesel generator
    • Loss of electrical power
    • Reduced electrical generating capacity
    • Personnel injury
  10. MDGGM Actions
    • CONTROLLING ACTIONS: NONE
    • IMMEDIATE ACTIONS:
    • A. RCO split electrical plant, determine and E-Stop affected SSDG
    • B. RCO start standby SSDG
    • C. RCO close standby SSDG generator breaker
    • D. RCO parallel unaffected SSDG with standby SDDG & establish stable electrical plant (ring bus)
    • E. RCO report to OOD "Governor Malfunction No_ SSDG, No_ SSDG started and paralleled to bus"
    • F. RCO order CRT to man affected space
    • G. When ordered, CRT man affected space
    • H. CRT report to RCO "Manned & Ready"