Reconstructed- Maximum allowed out-of-plumbness 653: 10.5.2.1
1/100 hieght
-
Corrosion- pH level that causes corrosion to increase 651: 5.3.2.1.g
< 5.0 pH
-
Corrosion- Chloride level where pitting on steel begins 651: 5.3.2.1.h
10 ppm
-
NDE- Weight used to check magnetic strength of an AC yoke V: T-762.b
10 lb
-
Grounding- Maximum electrical resistance permitted from tank to earth 575: 8.2.5
25 ohm
-
NDE- Min angle of eye-to-part to count as a visual exam
- 575: 9.2.1
- 577: 9.3.1
- 30 degrees
-
NDE- Weight used to check magnetic strength of a DC yoke V: T-762.c
40 lb
-
NDE- Minimum light intensity when performing non-fluorescent MT or PT exams
- V: T-676.3 & T-777.1
- 100 ft-candles
-
Vacuum box- Minimum light intensity when performing vacuum testing 650: 8.6.7
100 ft-candles
-
NDE- Minimum black light intensity when performing fluorescent MT or PT exams
- V: T-676.4.c & T-777.2.c
- 1000 micro-W/cm2
-
Brittle- Shell stress when brittle fracture is NOT a concern 653: Fig 5.1
< 7000 psi
-
NDE- Hole size that must be visible in RT when using a hole-type IQI V: Tbl-276
2T
-
Weld Qualification- Maximum allowed thickness on a WPS based on plate thickness (T) of a PQR test coupon IX: QW 451.1
2T
-
Weld Qualification- The "all position" test coupon IX: QW 461.9
6G
-
NDE- Lead letter used during RT to check for backscatter radiation V: T-223
B
-
NDE- Lead letter used during RT to indicate a film-side IQI V: T-277.b
F
-
NDE- Lead letter used during RT to indicate a repaired weld 653: 12.2.3.2
R
-
Repairs- Material where pre-heat can be substituted for a required PWHT
-
Repairs- Materials where control deposition welding can be substituted for a required PWHT 653: 11.3.2.a
P1, P3, P4
-
Hot Taps- Nozzle thickness for hot tapped nozzles 653: Fig 9.14
Ext strong
-
Repairs- Welding processes that can be used when substituting Preheat or Controlled Deposition welding for a required PWHT
- 653: 11.3.1.b
- 653: 11.3.2.b
- SMAW, GMAW, FCAW, GTAW
-
Corrosion- In a corrosion cell, the part that corrodes 651: 4.1.1.a
Anode
-
Corrosion- In a corrosion cell, the part that doesn't corrode 651: 4.1.1.b
Cathode
-
Linings- Minimum surface prep prior to applying lining 652: 7.1
NACE 2 Near-white
-
Weld Qualification- Rejectable in RT when qualifying a welder IX: QW 191.1.2.2.a.1
Crack, LoF, IP
-
Weld Qualification- Which welding process can a welder NOT be qualified by RT/UT
-
Welding- Variable needed on WPS
- IX: QW 200.1.b
- Essential & Non-Essential
-
Welding- Variable needed on PQR
|
|