DNO revision

  1. WI-3
    Allows holder to work isolated protection or metering equipment.
  2. OP-3
    Allows holder to remove and replace LV cut out  fuses.
  3. GP.4
    States any person can object to do a job if safety issues arise and should be reported as such and it shall be resolved in an approved manner.
  4. Basic safety Rules 5, 6 & 8.
    5. Isolation on LV apparatus. Lock off/ notices.

    6. No signals or time intervals.

    8.ID to remain identifiable during duration of job.
  5. Responsibilities of Persons C
    • Work to safety rules,
    • restore supply,
    • complete paperwork,
    • instruct end user.
  6. What should you always complete before starting work?
    Carry out a risk assessment of the job.

    Safety check and

    Inspect tools.
  7. PSSI 12
    • Safety from system
    • Working/testing. LV app
    • Lock off/ signs/ fuse removal
    • Safety equipment.
  8. PSSI 17
    Test tools/ PPE to prevent danger.
  9. Basic safety signs - Prohibition
    Red. Must be complied with. Tells you that you can not do something.
  10. Basic safety signs - Warning
    Yellow. Warning of a hazard.
  11. Basic safety signs - Safe condition.
    Green. Safe notices showing information.
  12. Basic safety signs - Mandatory
    Blue. Must be adhered to.
  13. What paragraph in PSSI 12 talks about metering and metering accessories?
    12.3
  14. What are the dangers associated with LV Cut-outs,what to look out for.
    • Broken fuse carriers,
    • Burn & scorch marks,
    • Poor wiring,
    • Holes and gaps where fingers and instruments can access the cut out,
    • No earthing,
    • Reversed polarity,
    • Tampering.
  15. CNE
    TNCS 0.35 ohms

    PME
  16. SNE
    TNS 0.8 ohms
  17. How to use test lamps
    • Proving unit.
    • Single phase. Test L to N, L to E, N to E.
    • 3 Phase L to N, L to L

    lights: no light, normal, extreme bright light.
  18. Polarity testing
    Use either martindale or test lamps to indicate correct polarity.

    Ensure correct polarity at cut out and after meter.

    Reversed polarity is dangerous and requires immediate attention.
  19. Phase rotation
    Brown > Black > Grey

    Phases are 120 degrees apart.
  20. What sort of cables would you expect to find at the cut out?
    • Before cutout single phase armoured, steel wire armoured after cutout red and black grey double insulated 10mm 16mm 25mm.
    • Earthing cables green and green and yellow.
  21. What are the new 3 phase and neutral colour codes?
    Phase - brown, black, grey

    neutral - blue.
  22. What are the old 3 phase colour codes?
    Phase - Red, Yellow, Blue

    Neutral - Black
  23. What PPE is required when working on Scottish Power Equipment?
    • Face mask,
    • Fireproof clothing,
    • Insulated rubber gloves,
    • Leather gauntlets,
    • Safety boots,
    • Fire retardant Apron,
    • Safety glasses
  24. What type of insulated rubber gloves should be worn?
    Class 1 is required.
  25. What voltage are the gloves rated to
    7500v
  26. What is the shelf life of the insulated rubber gloves?
    1 year
  27. How long can you use your insulated rubber gloves?
    6 months use or less if damaged.
  28. What voltage are the insulated tools rated to?
    1000V
  29. What is isolation? How to control and identify the Point of isolation.
    Disconnected by an isolating device in the isolating position, or by adequate physical separation or sufficient gap.