giusp - gas fires

  1. Gas Fires (including flueless fires) and/or Fireplace Builders opening inadequately sealed.
    AR

    There should be no gaps within the builders opening other than the fireplace opening and the flue itself.
  2. Gas Fires (including flueless fires) and/or Fireplaces. Gas fire fitted to letterbox opening or with inadequate catchment space.
    AR
  3. Gas Fires (including flueless fires) and/or Fireplaces. No closure plate fitted (where required), or inadequately sealed.
    AR
  4. Gas Fires (including flueless fires) and/or Fireplaces. Gas fire fitted on carpet - burner less than 225mm above carpet with damage evident
    AR
  5. Gas Fires (including flueless fires) and/or Fireplaces. Gas fire fitted on carpet - burner less than 225mm above carpet where no damage is evident.
    NCS
  6. Gas Fires (including flueless fires) and/or Fireplaces. Gas fire with a re-painted case, showing heat damage not caused by spillage.
    AR
  7. Gas Fires (including flueless fires) and/or Fireplaces. Gas fire with a re-painted case, showing no signs of heat damage evident.
    NCS
  8. Gas Fires (including flueless fires) and/or Fireplaces. Combustible materials located within builders opening and showing signs of heat damage or scorching.
    AR
  9. Gas Fires (including flueless fires) and/or Fireplaces. Combustible material is found to be located within a builder's opening and showing no signs of distress.
    NCS
  10. Gas Fires (including flueless fires) and/or Fireplaces. Flueless gas fire installed in a room or internal space where the air vent is incorrectly positioned.
    NCS

    Refer to manufacturers installation instructions for correct positioning.
  11. Combined Gas Fire Back Boilers and Back Boiler Units. Builder's opening that is not sealed i.e. around the flue liner, water and/or gas pipework.
    AR

    Seal all unsealed openings, i.e around flue liner, water and/or gas pipework.