Where
a flexible cord is used to supply a room air conditioner, the length of such cord shall not exceed
________mm for a nominal 120 volt
rating
3000 mm
-
Where
a flexible cord is used to supply a room air conditioner, the length of such cord shall not exceed
________mm for a nominal 208- or 240
volt rating.
1800 mm
-
An
overcurrent protective device of adequate short circuit rating that will open simultaneously all ungrounded conductors shall be applied in the grounding
autotransformer branch circuit and shall be rated or set at a current
not exceeding ________ percent of the
autotransformer continuous per phase current rating
125percent
-
An
overcurrent protective device of adequate short circuit rating that will open
simultaneously all ungrounded conductors
shall be applied in the grounding autotransformer branch circuit and shall be
rated or set at a current not exceeding ________ percent of the continuous current rating of any series
connected devices in the autotransformerneutral connection
42 percent
-
A
________ system that will cause the opening of the main switch or common
trip overcurrent device for the 3-phase,
4wire system shall be provided to guard against single phasing or internal
faults
Fault-Sensing system
-
If
the current-interrupting device is separate from the motor compressor and its
control circuit is operated by a protective device integral with the
motor-compressor, it shall be ________ so that the opening of the control
circuit will result in interruption of current to the motor-compressor
ARRANGED
-
Motor-compressor’s
attachment plug and receptacle rating shall not exceed ________ amperes at 125
volts
20 Amperes
-
Motor-compressor’s
attachment plug and receptacle rating shall not exceed ________ amperes at 250
volts
15 Amperes
-
An
attachment plug and receptacle shall be permitted to serve as the ________ for
a single phase room air conditioner rated 250 volts or less if the manual
controls on the room air conditioner are readily accessible and located within ________ mm of the floor
- Disconnecting means
- 1800 mm
-
Branch
circuit conductors supplying a single motor-compressor shall have an
ampacity not less than ________ percent of either the motor-compressor
rated-load current or branch-circuit selection current, whichever is greater
125 percent
-
A motor-compressor controller
shall have both a ________ full-load
current rating and a ________ current
rating not less than the nameplate rated-load current or branch-circuit
selection current, whichever is greater and locked-rotor current, respectively of the compressor
- Continuous Duty
- and a locked-rotor current
-
A
controller, serving more than one
motor-compressor or motor-compressor
and other loads , shall have a ________ full-load current rating and a locked-rotor current rating not less than the ________
- Continuous Duty
- Combined Load
-
Conductors supplying one or more motor-compressorwith or without an additional loads shall have
an ampacity not less than the sum
of the rated load or ________
ratings whichever is larger of all the motors plus the ________ currents of the other motors plus ________ percent of the highest motor or
motor-compressor rating in the group
- branch-circuit selection current
- plus full-load currents
- plus 25 percent
-
The
ampacity of the conductors supplying multi
motor and combination load
equipment shall not be less than the minimum circuit ampacity ________
on the equipment
Marked
-
For small
motor-compressor not having the locked-rotor current marked on the nameplate or for small motor not
covered by tables 4.30.14.1,
4.30.14.2, 4.30.14.3, 4.30.14.4,
the locked-rotor current shall be assumed ________ times the rated-load current.
6 times
-
An air
conditioning or refrigerating system shall be considered to be
a ________ under the provisions of
section 4.30.7.7
Single Machine
-
________ is the value in amperes to be used instead
of the rated load current in determining the ratings of the motor branchcircuit conductors, disconnecting mans, controllers,
and branch circuit short-circuit and ground
fault protective devicewherever the running overload protective device
permits a sustained currents greater than the specified percentage of the rated
load current
Branch-circuit Selection current
-
The
value of branch-circuit selection current
willalways be ________ or
________ than the marked rated-load
current
EQUAL TO or GREATER THAN
-
The value of
branch-circuit selection current willalways beEqual to or Greater than the marked ________ current
Rated-load current
-
A
combination consisting of a compressor
and motor, both of which are enclosed
in the same housing, with no external shaft or shaft seals,
the motor operating on the refrigerant
Hermetic Refrigerant motor-compressor
-
Hermetic
Refrigerant motor-compressor is a combination consisting of a compressor and motor, both of which are enclosed in the same housing, with no
external shaft or shaft seals, the motor operating on the________
Refrigerant
-
The
Rated-Load current for a Hermetic
Refrigerant motor-compressor is the current resulting when the motor-compressor
is operated at the rated ________ ; rated ________; and rated ________ of the
equipment it serves
- Rated load
- Rated voltage
- Rated Frequency
-
The
frames of portable motors that operates at over 150 volts to ground shall be ________ or ________
GUARDED or GROUNDED
-
Instruments
transformer secondaries and exposed non-current carrying metals
or other conductive parts or cases ofinstruments transformers, meters,
instruments, and relays shall be
________
GROUNDED
-
Controllers
enclosures shall be grounded regardless of
________
regardless of VOLTAGE
-
Where
no rated-load current is shown on the equipment nameplate, the ________ current
shown on the compressor nameplate shall be used
Rated-Load current
-
EXCEPTION: where so marked, the Branch-circuit Selection current shall be used instead
of ________ current in determining the highest rated ( Largest ) motor- compressor
Rated-Load current
-
Dry-type transformers rated over ________ volts shall be installed in a vault
complying with part 4.50.3
35 000 volts
-
Section 4.90.5
Electrode-Type Boiler. (Ground
Current Detection). Means shall provided for detection of the sum of the neutral and
ground currents and shall trip the circuit interrupting device if the sum of those currents exceeds the
greater of5 amperes or ________ percentof
the boiler full load current for ________ seconds or exceeds an instantaneous value of 25percent
of the boiler full load current
-
Section 4.90.5
Electrode-Type Boiler. (Ground
Current Detection). Means shall provided for detection of the sum of the neutral and ground
currents and shall trip the circuit interrupting device if the sum of those currents exceeds the greater of ________amperes or 7 ½ percentof the
boiler full load current for 10 seconds
or exceeds an instantaneous value of ________ percent of the boiler full load
current
-
A separate overload
relay
protecting a single motor-compressor against overload and failure to start
shall be selected to trip at not more than ________ percent of the
motor-compressor rated-load current
140 percent
-
The ________ markings
of cord and plug connected equipment
rated not greater than 250 volts, single
phase, such as household refrigerators and freezers, Drinking
water cooler and beverage dispenser, shall be used in determining
the branch circuits requirements and each unit shall be considered as a ________
unless the nameplate is marked otherwise
- Nameplate Markings
- Single Motor
-
The
ampere rating of hermetic refrigerant motor-compressor’s disconnecting means shall be at least ________ percent of the
rated-load current or branch circuit selection current, whichever is greater
115 percent
-
A room air conditioner shall be considered as
a ac appliance unit in determining its branch circuits and its rating is not more than ________ ampere and ________ volts
-
Where
live parts of motors or controllers operating at over 150 volts to ground
are GUARDED against accidental contact only by location as specified
in section 4.30.12.2 and where
adjustments or other attendance maybe necessary during the operation of the
apparatus, suitable ________ or ________ shall be provided so that the
attendant cannot readily touchlive parts unless standing on the MATS or PLATFORMS
INSULATING MATS or PLATFORMS
-
Ultimate trip current of overcurrent
(overload) relays or other motor protective devices used for the motor control
apparatus shall not exceed ________ percent of the controllers continuous
current rating
115 percent
-
Where
the motor branch circuit disconnecting means is separate from the controller, the disconnecting means current rating shall
not be less than the ________ setting of
the overcurrent relays in the circuit
115 percent
-
Flexible metal
conduit or
liquid tight Flexible metal conduitnot
exceeding ________ mm in length shall be
permitted to be employed for raceway connection to a motor terminal
enclosure
1800 mm
-
(GENERAL) : The disconnecting means for motor circuits rated 600 volts, nominal
or less, shall have an ampere rating of at least ________ percent of the full-load current
rating of the motor
115 percent
-
GENERAL : ( Exception) a
listed non-fused motor circuit switch having a horse power rating equal to or
greater than the motor horse power shall be permitted to have an ampere rating
less than ________ percent of the full-load current rating of the motor
115 percent
-
Disconnecting
means for torque motors shall
have an ampere rating of at least
________ percent of the motors
nameplate current
115 percent
-
Disconnecting
means for torque motors shall
have an ampere rating of at least 115
percent of the motors ________
Nameplate current
-
In phase arrangements of Bus
Bars and Conductors, the
________ phase shall be that phase having the HIGHER VOLTAGE to ground on 3-phase, 4wire delta-connected
system
B phase
-
In phase arrangements of Bus
Bars and Conductors, the “B phase”
shall be that phase having the ________on 3-phase, 4wire
delta-connected system
Higher Voltage to Ground
-
In phase arrangements of Bus
Bars and Conductors, the “B phase”
shall be that phase having the HIGHER
VOLTAGE to ground on
________system
3-phase, 4wire delta-connected
-
The
phase arrangement on 3-phase horizontal common power and vertical buses shall
be ________, ________, ________ from Front to Back,
Top to Bottom or Left to Right , as viewed from the front of the
Motor Control Center
A, B, C
-
The
phase arrangement on 3-phase horizontal common power and vertical buses shall
be A, B, C from Front to Back,Top to BottomorLeft
to Right , as viewed from the________ of the Motor Control Center
FRONT
-
The
phase arrangement on 3-phase horizontal common power and vertical buses shall
be A, B, C
from________, ________, ________ , as viewed from the front of the Motor Control Center
- Front to Back
- Top to Bottom or
- Left to Right
-
(Exception) :Rear-mounted
units connected to vertical bus that is common to front- mounted units, shall be permitted to have a ________
phase arrangement where properly
identified
C, B, A phase arrangement
-
Where
used as service equipment, each motor
control center shall be provided with a single main disconnecting means to disconnect all ________ service
conductors
UNGROUNDED Service Conductor
|
|