Master Stream
1 1/4"
415
Master Stream
1 3/8"
502
Master Stream
1 1/2"
597
Master Stream
1 5/8"
701
Master Stream
1 3/4"
813
Master Stream
2"
1062
Hand Held Smooth Bore
15/16"
180
Hand Held Smooth Bore
1"
210
Hand Held Smooth Bore
1 1/8"
265
Hand Held Smooth Bore
1 1/4"
328
E.P.( Elevation Pressure)=
.5 x H
F.L.=
C (Q)2L
% Drop
(Static - Residual)100/ Static
C - 1"
150
C - 1 1/2"
24
C - 1 3/4"
15.5
C - 2 1/2"
2
C - 3"
.8
C - 3 1/2"
.4
C - 4"
.2
Siamese Co
2 - 2 1/2"
.5
Siamese Co
3 - 2 1/2"
.22
Siamese Co.
1- 3", 1- 2 1/2"
.3
Siamese Co
1- 3", 2- 2 1/2"
.16
Portable Monitors
25 psi
Standpipe
25 psi + back pressure
Ladder Pipe
80 psi
Pump Capacity
150 psi
100%
Pump Capacity
200 psi
70%
Pump Capacity
250 psi
50%
Pressure Drop
0-10
3x
Pressure Drop
11-15
2x
Prssure Drop
16-25
1x
Pressure Drop
25+
May support additional lines
E.P. Booster lines at 30 gpm
130 psi
Sprinkler Connection
150 psi
125 psi for older systems
When pumping to a supply line or relay use an inlet pressure of?
20 psi