WAC 45 minimum approach distances

  1. 0-50v
    • Phase to ground: Not specified
    • Phase to Phase: Not specified
  2. 51-300v
    • Phase to ground: avoid contact
    • Phase to Phase: avoid contact
  3. 301-750
    • Phase to ground :1'0
    • Phase to Phase: 1'0
  4. 751 to 15 kv
    • Phase to ground: 2'2
    • Phase to Phase: 2'3
  5. 15.1 to 36 kv
    • Phase to ground: 2'7
    • Phase to Phase: 2'10
  6. 36.1 to 46 kv
    • Phase to ground: 2'9
    • Phase to Phase: 3'2
  7. 46.1 to 72.5 kv
    • Phase to ground: 3'3
    • Phase to Phase: 3'11
  8. 72.6 to 121 kv
    • Phase to ground: 3'2
    • Phase to Phase: 4'3
  9. 138 to 145 kv
    • Phase to ground: 3'7
    • Phase to Phase: 4'11
  10. 161 to 169 kv
    • Phase to ground: 4'0
    • Phase to Phase: 5'8
  11. 230 to 242 kv
    • Phase to ground: 5'3
    • Phase to Phase: 7'6
  12. 345 to 362 kv
    • Phase to ground: 8'6
    • Phase to Phase: 12'6
  13. 500 to 550 kv
    • Phase to ground: 11'3
    • Phase to Phase: 18'1
  14. 765 to 800 kv
    • Phase to ground: 14'11
    • Phase to Phase: 26'