9 parts of a pump
Impeller
Eye
Hub
Shroud
Vanes
Volute
Casing
Stripping edge
Discharge
PDP equation
PDP = NP + FL + AL + +/- EL
Fog Nozzle pressure
100 PSI
Solid bore hand held NP
50 psi
Solid bore monitor NP
80 PSI
Gates/manifolds appliance loss
10 psi (after 350 gpm)
Foam eductor apliance loss
200 PSI?
Monitor appliance loss
25 psi
Lapper pipe appliance loss
25 psi
Deck gun PDPs
Solid bore- 105 psi
Fog nossle- 125 psi
1 3/4" FL at 150 gpm (100')
35 psi FL
1 3/4" FL at 200 gpm (100')
62 psi FL
2 1/2" FL at 150 gpm (100')
5 psi FL
2 1/2" FL at 200 gpm (100')
8 psi FL
2 1/2" FL at 210 gpm (100')
9 psi FL
2 1/2" FL at 250 gpm (100')
12.5 psi FL
2 1/2" FL at 265 gpm (100')
14 psi FL
2 1/2" FL at 300 gpm (100')
18 psi FL
2 1/2" FL at 325 gpm (100')
18 psi FL
2 1/2" FL at 400 gpm (100')
32 psi FL
2 1/2" FL at 500 gpm (100')
50 psi FL
5" FL at 265 gpm (100')
0.5 psi FL
5" FL at 300 gpm (100')
1 psi FL
5" FL at 325 gpm (100')
1 psi FL
5" FL at 400 gpm (100')
1.5 psi FL
5" FL at 500 gpm (100')
2 psi FL
5" FL at 600 gpm (100')
3 psi FL
5" FL at 800 gpm (100')
5 psi FL
5" FL at 1000 gpm (100')
8 psi FL
Fog Nozzle GPMs
1 3/4"- 150-200
2 1/2"- 250-300
Monitor- 1000
Hand-held solid bore tip GPMs
1"- 210
1 1/8"- 265
1 1/4'- 325
Monitor tip gpms
1 3/8"- 500
1 1/2"- 600
1 3/4"- 800
2"- 1050