Home
Flashcards
Preview
Fuel Pool Cooling
Home
Get App
Take Quiz
Create
What is the power supply for the FPC pumps?
MCC-133 and MCC-43
What are all of the Emergency Make-up sources to the Spent Fuel Pool?
Condensate Service Stations/Demin or Firehose
Filter demin back wash connection
RHRSW via RHR
Fire Water via RHR
Precoat Pump
RHR suction from Torus
Assumptions for Normal Refueling Outage Discharge Heat Load?
Assumes 141 bundles are dishcarged every 18 mos, 96 hrs of cooling have occurred.
Heat load per discharge batch is 5.6 mil BTU/hr
Heat load decreases rapidly
The next disch to the HDFSS adds another 5.6 mil BTU/hr
Assumptions for Full Core Discharge?
Discharge is req'd 30 days following the last refueling discharge and fills the final 484 spaces in the HDFSS.
Full core disch is completed within 150 hrs of shutdown.
Calculated heat load is 19 mil BTU/hr, RHR would be used, as necessary, in order to cool the full-core discharge.
High Level Alarm for Skimmer surge tank?
Low Level Alarm?
Lo Lo Level?
8'
4'
2'6" - and trips pumps.
Fuel Pool Level Alarms?
Hi - 37'11-5/8"
Lo - 36'7"
What is the cooling medium for the FPCC HX's?
RBCCW
Refuel Bellows Seal Lkg?
Rx Level Seal Lkg?
Fuel Pool Gate Lkg?
0.75 GPM
3 GPM
1 GPM
Minimum allowed SFP by Tech Specs?
The spent fuel storage pool water level shall be ≥ 37 ft above the bottom of the spent fuel storage pool.
Author
blinkgold311
ID
100057
Card Set
Fuel Pool Cooling
Description
fuel pool cooling
Updated
2011-09-06T13:49:31Z